User Manual

Siemens Building Technologies Application :22 RWD82/22 - 05.2001
HVAC Products RWD82 1
RWD82/22
RWD82 Universal Controller
Application 22
Absolute limit control
Room temperature control
Two stage electric heating
Control 2 stage digital
Room temperature control
Two stage ON / OFF electrical heating
Absolute maximum and / or minimum limit control of the supply air.
Optional day / night set point adjustment .
S1
X1
X2
D1
Q1
Q2
CP
........RWD82.......
M1
RWD82/22
X1
X2
S1
Q1
Q2
PC
HLT
PS
HR
Room temperature sensor
Limit temperature sensor
Time clock or switch
First stage electric air heater
Second stage electric air heater
Personal computer
High limit thermostat
Pressure switch
Heater relay
X1
Universal analogue input - main sensor
Auxiliary analogue input
Digital input
Digital output
Communication port
P
HLT
PS
T
T
Digital output
HR
X2
T
Room temperature sensor can be selected as Ni1000, Pt1000, or active sensor.
Adjustable differential of digital output Q1.
Adjustable set point of Q1.
Adjustable differential of digital output Q2.
Adjustable set point of Q2.
24Vac controller supply voltage
Duct temperature sensor can be selected as Ni1000, Pt1000, or active sensor.
Absolute maximum and / or minimum supply air temperature control.
Day / night set points can be selected via time clock or switch.
Independent mode for the two heating outputs.
A high limit manual reset thermostat is mounted downstream of the air electric heater,
and de-energises the heater on excessive duct temperatures. This thermostat has to
be manually reset following detection of overheating. It is often supplied by the
supplier of the electric heater.
A pressure switch is also specified to detect loss of static pressure in the duct,
indicating loss of fan. This also de-energises the electric heater but it is auto reset and
allows electric heater function following the detection of fan operation.
These safety units can be connected directly in series with small electric heaters, but
for larger electric heaters they are connected to a heater contactor switching the
electric heater.
Supplemental features
Control
Operating modes
Safety functions

Summary of content (3 pages)