Siemens Building Technologies Application :64 RWD82/64- 02.2001
HVAC Products RWD82 1
RWD82/64
RWD82 Universal Controller
Application 64
Compensation shift
Room temperature control
Refrigeration solenoid valves
Control 2 stage digital
Room temperature control
Two stage ON / OFF refrigeration cooling
Outside air compensation of the room temperature .
Optional day / night set point adjustment .
S1
X1
X2
D1
Q1
Q2
CP
........RWD82.......
M1
Q1
RWD82/64
X1
X2
S1
Q1
Q2
PC
Room temperature sensor
Outside air temperature sensor
Time clock or switch
Refrigeration solenoid valve
Refrigeration solenoid valve
.
Personal computer
X1
Universal analogue input - main sensor
Auxiliary analogue input
Digital input
Digital output
Digital output
Communication port
T
Q2
X2
T
• Room temperature sensor can be selected as Ni1000, Pt1000, or active sensor.
• Two stage on / off cooling
• Adjustable differential of digital output Q1.
• Adjustable set point of Q1.
• Adjustable differential of digital output Q2.
• Adjustable set point of Q2.
• 24Vac controller supply voltage
• Outside air temperature sensor can be selected as Ni1000, Pt1000, or active sensor.
• Outside air compensation of the room temperature set point.
• Day / night set points can be selected via time clock or switch.
• Independent mode for the two cooling outputs.
Supplemental features
Control
Operating modes