Siemens RWD Primary Controls Modbus Interface CB1P3099en_01
Building Technologies RWD Parameters & Addresses 27.10.2009
RWD
Parameter
Addresses
RWD
Parameters
Data Format Detailed Descriptions & Data Interpretation
30 to 130: 30 to 130
If the TempUnit is F,
0: OFF
86 to 266: 86 to 266
40195 * T_Abs IEEE754 The absolute charging temperature
If the TempUnit is C,
30 to 90 representing 30 to 90
If the TempUnit is F,
86 to 194 representing 86 to 194
40197 * D_SP IEEE754 Delta Set Point
If the TempUnit = C,
0 to 40 representing 0 to 40
If the TempUnit =F,
0 to 80 representing 0 to 80
40199 LIMMAX_Abs IEEE754 Maximum of Absolute Limiter
(Used in RWD32/6268/82,
application no = 12, 22, 32, etc.)
40201 LIMMIN_Abs IEEE754 Minimum of Absolute Limiter
(Used in RWD32/6268/82,
application no = 12, 22, 32, etc.)
40203 LIMMAX_Rel IEEE754 Maximum of Rel Limiter
(Used in RWD32/6268/82,
application no = 13, 23, 33, etc.)
40205 LIMMIN_Rel IEEE754 Minimum of Rel Limiter
(Used in RWD32/6268/82,
application no = 13, 23, 33, etc.)
40207 XP3 IEEE754 P Band for Cooling 1
40209 XP4 IEEE754 P Band for Cooling 2
40211 XP4_cas IEEE754 P Band for cascade Cooling 2
40213 XP2_cas IEEE754 P Band for cascade Heating 2
40215 * XDZ_AppB IEEE754 Dead Zone for,
RWD32/82 application no = 61
RWD68 application no = 71
40217 * XDZ_AppC IEEE754 Dead Zone for,
RWD32/82 application no = 21
RWD68 application no = 31