Data Sheet for Product

11 / 24
Siemens Superheat Controller CE1N3372en_02
Smart Infrastrucutre 2022-02-16
Following the initial power up, the controller automatically enters the configuration
mode. In this mode, the type of refrigerant is selected and the unit of temperature
°C or °F and pressure Bar or Psi determined.
Optionally, control of the cooling capacity can be configured.
To reconfigure the controller, refer to "Selection of operation mode" above.
Function
Parameter code
Adjustable Range / Increment
Default Value
Selection of refrigerant
REFRIG
R22, R23, R32, R125, R12YF, R12ZE, R134a,
R152a, R170, R227E, R236F, R245F, R290,
R401A, R401B, R401C, R402A, R402B, R404A,
R406A, R407A, R407B, R407C, R407F, R408A,
R409A, R410A, R410B, R413A, R417A, R421A,
R422A, R422D, R427A, R434A, R437A, R438A,
R444B, R447B, R448A, R449A, R450A, R452B,
R454B, R502, R507, R513A, R600, R600a, R717,
R723, R744, R1270
-
Enable / disable com-
pressor and EIV feed-
back signal
ENABLE
1)
COMP
(compressor)
For circuit 1: ON
ON
For circuit 2: ON, OFF
OFF
Fb (EIV feedback)
ON, OFF (only for Circuit1)
OFF
Selection of application
CAP
2)
(see page 3)
NO (simple superheat)
EXT (external capacity control)
INT(internal capacity control)
NO
Types of sensors
SENSOR
X1
QBE9103-P10U /-P30U/-P60U
with 4…20 mA output signal;
QBE2004-P10U /-P25U/-P60U
with 0…10 V output signal
QBE9103-P10U
X2
Ni1000
Ni1000
X3
0…10 V, 4…20 mA
0…10 V
X4
For configured internal capacity (Circ. 1): NO,
0…10 V, 4…20 mA;
For configured external capacity (Circ. 1): 0…10 V,
4…20 mA;
Only for enabled Circuit 2:
QBE2004-P10U/-P25U/-P60U
with 0…10 V output signal, or
QBE9103-P10U/-P30U/-P60U
with 4…20 mA output signal
-
X5
Ni1000
-
Measurement range
RANGE
3)
X4
LO (low limit):
-90.0…90.0 °C / 0.1 °C
-130.0...194.0 °F / 0.1 °F
-35.0 °C
-31.0 °F
HI (high limit):
-90.0…90.0 C/ 0.1 °C
-130.0...194.0 °F / 0.1 °F
+35.0 °C
+95.0 °F
Selection of units
UNITS
T (temperature)
°C (K), °F
°C (K)
P (pressure)
Bar, Psi
Bar
EIV (valve opening)
V, %
%
1) The compressor of Circuit 1 is the default working unit and cannot be disabled. EIV feedback signal is
only available for Circuit 1.
2) Can be parameterized only if external or internal capacity control has been selected in the configura-
tion mode.
3) The range limit (RANGE) can be configured only if internal capacity control (application 3) and X4
have been selected.
If the wrong type of refrigerant is selected, the plant can be damaged!
Configuration mode
[CONF]
Notes
Parameter list
Important