Data Sheet for Product

14 / 24
Siemens Superheat Controller CE1N3372en_02
Smart Infrastrucutre 2022-02-16
Mounting and Installation notes
For mounting and electrical installation, the following notes should be observed.
A Mounting on DIN rail
No additional parts are required.
B Wall mounting
With four ellipse screws for holes with diameter of
4 mm x 6 mm
C Flush panel mounting
With HVAC Products ARG462.10 mounting kit
Mounting Instruction M 3351.1
The wiring can be made with standard cables. Shielded cables are recommended
only if the controller is exposed to strong electromagnetic fields (EMC).
The PolyCool™ RWR462.10/ALG controller operates on AC / DC 24 V (max. 10
VA) extra low voltage and is short-circuit-proof
The operating voltage must satisfy the requirements for safety extra low voltage
(SELV) conforming to EN 60 730
The transformers used must be safety transformers with double insulation con-
forming to EN 60 742. They must be designed for 100 % duty. When using sev-
eral transformers in the system, terminals G0 must be galvanically interconnect-
ed
If voltages of more than AC 24 V +20 % (DC 24V +10 %) are fed to the low volt-
age terminals, the controller or other connected devices can be damaged be-
yond repair. Also, voltages exceeding 42 V represent an electric shock hazard
Mains voltages up to AC 250 V may only be fed to the potential-free contact Q13
Controller
Electrical installation