Data Sheet for Product

17 / 24
Siemens Superheat Controller CE1N3372en_02
Smart Infrastrucutre 2022-02-16
Configuration of DIP Switches for analogue inputs (X…)
The default factory settings of DIP switches at the rear top of the controller are
presented as follows. Bit 1 of J2 is used for factory calibration.
To wire the terminals with different types of sensors, configure the DIP Switches as
follows.
Bit 4 of J1
Bit 5 of J1
Bit 6 of J1
4…20 mA
420 mA
Off
On
Off
010 V
On
Off
Off
0…10 V
Bit 2 of J1
Bit 3 of J1
Ni1000
Ni1000
On
Off
Bit 7 of J2
Bit 8 of J2
Bit 1 of J1
4…20 mA
420 mA
Off
On
Off
010 V
On
Off
Off
0…10 V
Bit 4 of J2
Bit 5 of J2
Bit 6 of J2
4…20 mA
420 mA
Off
On
Off
010 V
On
Off
Off
0…10 V
Bit 1 of J2
Bit 2 of J2
Bit 3 of J2
Ni1000
Ni1000
Off
On
Off
To meet the plant-specific requirements, the controller must be configured by au-
thorized staff that must also set the relevant parameters:
The project-specific data must be transferred to the controller. The Installation
and User Manual contains the step-by-step procedure which must be followed
During commissioning, fault messages can occur (don't pay attention to them).
On completion of commissioning, fault messages must no longer be pre-
sent!
The values and settings entered on the controller are saved in non-volatile
memory even in the event of a power failure.
Configuration of
DIP Switches
For X1
For X2
For X3
For X4
For X5
Configuration and pa-
rameter settings
Notes