Data Sheet for Product

3 / 24
Siemens Superheat Controller CE1N3372en_02
Smart Infrastrucutre 2022-02-16
Peripheral devices
The PolyCool™ superheat controller uses two types of sensors and one valve
made by Siemens HVAC Products.
Field devices
Type
Measuring range
Signal
Data sheet no.
Cable Temperature
Sensor
QAZ21.682/101
-50…80° C
Resistance sensor
LG-Ni 1000
N1848
Pressure sensor
- QBE9103-P10U*
- QBE9103-P30U*
- QBE9103-P60U*
- QBE2004-P10U
- QBE2004-P25U
- QBE2004-P60U
-1…9 bar
-1…29 bar
-1…59 bar
-1…9 bar
-1…24 bar
-1…59 bar
DC 4…20 mA
DC 4…20 mA
DC 4…20 mA
DC 0…10 V
DC 0…10 V
DC 0…10 V
A6V10451440
A6V10434676
Refrigerant valve
-MVL661..-../ MVS661.25-..
DC 0…10 V
N4714/N4717
* Replacement sensor for service QBE2104-P10U / P30U / P60U
The controller and the above mentioned peripheral devices have been matched to
the application covered by this data sheet. Therefore, valve and sensors may not
be replaced by products of other manufacture.
Safety transformer (25 VA) to EN 60 742 is not included in the delivery.
Configurable functions
The controller's functions are preconfigured. By changing the parameters, the func-
tions can be matched to the type of plant.
Control of the evaporator is based on true superheat control. For this purpose,
pressure P0 acquired at the evaporator output is converted to the respective tem-
perature of the refrigerant used.
The controller contains the polynomials of the following types of refrigerants:
R22
R23
R32
R125
R1234yf
1)
R1234ze
2)
R134a
R152a
R170 *
R227ea
3)
R236fa
4)
R245fa
5)
R290 *
R401A
R401B
R401C
R402A
R402B
R404A
R406A
R407A
R407B
R407C
R407F
R408A
R409A
R410A
R410B
R413A
R417A
R421A
R422A
R422D
R427A
R434A
R437A
R438A
R444B
R447B
R448A
R449A
R450A
R452B
R454B
R502
R507
R513A
R600 *
R600a *
R717 **
R723
R744
R1270 *
1) Displayed as R12YF
2) Displayed as R12ZE
3) Displayed as R227E
4) Displayed as R236F
5) Displayed as R245F
* Hydrocarbons: Can only be used for explosion-proof valves!
** R717 (NH3): Requires the use of valves suited for ammonia, e.g. MVS661.25-
The temperature can be displayed in °C (K) or °F , and the pressure in Bar or Psi.
EIV opening can be displayed in V or %.
Siemens
HVAC Products
Note
Selection of
refrigerant
Important
Selection of units