Data Sheet for Product

5 / 24
Siemens Superheat Controller CE1N3372en_02
Smart Infrastrucutre 2022-02-16
EN
EIV
KP
AL
Internal Capacity Control (2)
D1 Q14 Y1X3
Y1X
X5
Ni1000
TM
RWR462.10
1-4
X1 X2
PO
p
t
TOH
EN
EIV
KP
AL
Two Superheat Circuits
D1 Q14
Y1X
EIV
KP
Y2
EN
AL
D2 Q24
X1 X2Y1X3
X4 X5Y2
RWR462.10
TOHPO
PO TOH
1-4
p
t
1-4
p
t
This controller can be applied to two pure superheat control circuits, but only one
EIV feedback can be input (terminal X3). The simulation mode is possible for one
circuit only (for simulation mode, refer to pages 7 and 12).
The superheat controller monitors the temperature differential between the suction
gas temperature and the calculated evaporation temperature (TOH-TO) to maintain
the adjusted setpoint
T.
The electronic injection valve is controlled via analogue output Y1 (Y2 for Circuit 2).
Y
T (TOH-TO)
T SP
100%
0%
3372D02E
EIV
Setpoint of superheat
Two superheat circuits
Note
Superheat control