Technical Specifications
The S7-200 CPUs and all S7-200 expansion modules conform to the technical
specifications listed in Table A-1.
Table A-1 Technical Specifications for the S7-200 Family
Environmental Conditions — Transport and Storage
IEC 68-2-2, Test Bb, Dry heat and
IEC 68-2-1, Test Ab, Cold
-40° C to +70° C
IEC 68-2-30, Test Db, Damp heat 25° C to 55° C, 95% humidity
IEC 68-2-31, Toppling 100 mm, 4 drops, unpacked
IEC 68-2-32, Free fall 1 m, 5 times, packed for shipment
Environmental Conditions — Operating
Ambient Temperature Range
(Inlet Air 25 mm below unit)
0° C to 55° C horizontal mounting
0° C to 45° C vertical mounting
95% non-condensing humidity
IEC 68-2-14, Test Nb 5° C to 55° C, 3° C/minute
IEC 68-2-27 Mechanical shock 15 G, 11 ms pulse, 6 shocks in each of 3 axis
IEC 68-2-6 Sinusoidal vibration 0.30 mm peak-to-peak 10 to 57 Hz; 2 G panel mount, 1 G DIN rail mount,
57 Hz to 150 Hz; 10 sweeps each axis, 1 octave/minute
EN 60529, IP20 Mechanical protection Protects against finger contact with high voltage as tested by standard
probes. External protection is required for dust, dirt, water, and foreign
objects of less than 12.5 mm in diameter.
Electromagnetic Compatibility — Immunity
1
per EN50082-2
1
EN 61000-4-2 (IEC 801-2)
Electrostatic discharge
8 kV air discharge to all surfaces and communication port
EN 50140 (IEC 801-3)
Radiated electromagnetic field
80 MHz to 1 GHz 10 V/m, 80% modulation with 1 kHz signal
EN 50141
Conducted disturbances
0.15 to 80 MHz 10 V RMS
80% amplitude modulation at 1kHz
EN 50204
Digital telephone immunity
900 MHz ± 5 MHz, 10 V/m, 50% duty cycle, 200 Hz repetition frequency
EN 61000-4-4 (IEC 801-4)
Fast transient bursts
2 kV, 5 kHz with coupling network to AC and DC system power
2 kV, 5 kHz with coupling clamp to digital I/O and communications
EN 61000-4-5 (IEC 801-5)
Surge immunity
2 kV asymmetrical, 1 kV symmetrical
5 positive/5 negative pulses 0°, +90°, -90° phase angle
(24 VDC circuits require external surge protection)
VDE 0160 Non-periodic overvoltage at 85 VAC line, 90° phase angle, apply 390 V peak, 1.3 ms pulse
at 180 VAC line, 90° phase angle, apply 750 V peak, 1.3 ms pulse