Specifications
S7-200 Specifications
A-13
S7-200 Programmable Controller System Manual
C79000-G7076-C233-01
Table A-3 Specifications for CPU 222 DC/DC/DC and CPU 222 AC/DC/Relay
Description
Order Number
CPU 222 AC/DC/Relay
6ES7 212-1BB20-0XB0
CPU 222 DC/DC/DC
6ES7 212-1AB20-0XB0
Input Features
Number of integrated inputs
Input type
8 inputs
Sink/Source (IEC Type 1 sink)
8 inputs
Sink/Source (IEC Type 1 sink)
Input Voltage
Maximum continuous permissible
Surge
Rated value
Logic 1 signal (minimum)
Logic 0 signal (maximum)
30 VDC
35 VDC for 0.5 s
24 VDC at 4 mA, nominal
15 VDC at 2.5 mA, minimum
5 VDC at 1 mA, maximum
30 VDC
35 VDC for 0.5 s
24 VDC at 4 mA, nominal
15 VDC at 2.5 mA, minimum
5 VDC at 1 mA, maximum
Isolation (Field Side to Logic Circuit)
Optical isolation (Galvanic)
Isolation groups of
500 VAC for 1 minute
4 points
500 VAC for 1 minute
4 points
Input Delay Times
Filtered inputs and interrupt inputs
0.2 to 12.8 ms, user-selectable 0.2 to 12.8 ms, user-selectable
HSC Clock Input Rate
Single Phase
Logic 1 level = 15 to 30 VDC
Logic 1 level = 15 to 26 VDC
Quadrature
Logic 1 level = 15 to 30 VDC
Logic 1 level = 15 to 26 VDC
20 kHz, maximum
30 kHz, maximum
10 kHz, maximum
20 kHz, maximum
20 kHz, maximum
30 kHz, maximum
10 kHz, maximum
20 kHz, maximum
Connection of 2 Wire Proximity Sensor (Bero)
Permissible leakage current
1 mA, maximum 1 mA, maximum
Cable Length
Unshielded (not HSC)
Shielded
HSC inputs, shielded
300 m
500 m
50 m
300 m
500 m
50 m
Number of Inputs ON Simultaneously
40 ° C
55 ° C
8
8
8
8
Output Features
Number of integrated outputs
Output type
6 outputs
Solid State-MOSFET
6 outputs
Relay, dry contact
Output Voltage
Permissible range
Rated value
Logic 1 signal at maximum current
Logic 0 signal with 10 K Ω load
20.4 to 28.8 VDC
24 VDC
20 VDC, minimum
0.1 VDC, maximum
5 to 30 VDC or 5 to 250 VAC
-
-
-
Output Current
Logic 1 signal
Number of output groups
Number of outputs ON (maximum)
Per group - horizontal mounting (maximum)
Per group - vertical mounting (maximum)
Maximum current per common/group
Lamp load
ON state resistance (contact resistance)
Leakage current per point
Surge current
Overload protection
0.75 A
1
6
6
6
4.5 A
5 W
0.3 Ω
10
µA, maximum
8 A for 100 ms, maximum
No
2.00 A
2
6
3
3
6 A
30 W DC/ 200 W AC
0.002 Ω, maximum when new
-
7 A with contacts closed
No