Specifications
S7-200 Specifications
A-19
S7-200 Programmable Controller System Manual
C79000-G7076-C233-01
Table A-4 Specifications for CPU 224 DC/DC/DC and CPU 224 AC/DC/Relay
Description
Order Number
CPU 224 AC/DC/Relay
6ES7 214-1BD20-0XB0
CPU 224 DC/DC/DC
6ES7 214-1AD20-0XB0
Isolation (Field Side to Logic)
Optical isolation (galvanic)
Isolation resistance
Isolation coil to contact
Isolation between open contacts
In groups of
500 VAC for 1 minute
-
-
-
5 points
-
100 M Ω, minimum when new
1500 VAC for 1 minute
750 VAC for 1 minute
4 points/3 points/3 points
Inductive Load Clamping
Repetitive Energy dissipation
< 0.5 LI
2
x switching rate
Clamp voltage limits
1 W, all channels
L+ minus 48V
-
-
Output Delay
Off to On (Q0.0 and Q0.1)
On to Off (Q0.0 and Q0.1)
Off to On (Q0.2 through Q1.1)
On to Off (Q0.2 through Q1.1)
2 µs, maximum
10
µs, maximum
15
µs, maximum
100
µs, maximum
-
-
-
-
Switching Frequency (Pulse Train
Outputs)
Q0.0 and I0.1
20 kHz, maximum 1 Hz, maximum
Relay
Switching delay
Lifetime mechanical (no load)
Lifetime contacts at rated load
-
-
-
10 ms, maximum
10,000,000 open/close cycles
100,000 open/close cycles
Cable Length
Unshielded
Shielded
150 m
500 m
150 m
500 m