Specifications
S7-200 Quick Reference Information
G-4
S7-200 Programmable Controller System Manual
C79000-G7076-C233-01
Table G-4 High-Speed Counters HSC0, HSC3, HSC4, and HSC5
Mode
HSC0 HSC3 HSC4 HSC5
Mode
I0.0 I0.1 I0.2 I0.1 I0.3 I0.4 I0.5 I0.4
0 Clk - - Clk Clk - - Clk
1 Clk - Reset - Clk - Reset -
2 - - - - - - - -
3 Clk Direction - - Clk Direction - -
4 Clk Direction Reset - Clk Direction Reset -
5 - - - - - - - -
6 Clk Up Clk Down - - Clk Up Clk Down - -
7 Clk Up Clk Down Reset - Clk Up Clk Down Reset -
8 - - - - - - - -
9 Phase A Phase B - - Phase A Phase B - -
10 Phase A Phase B Reset - Phase A Phase B Reset -
11 - - - - - - - -
Table G-5 High-Speed Counters HSC1 and HSC2
Mode
HSC1 HSC2
Mode
I0.6 I0.7 I1.0 I1.1 I1.2 I1.3 I1.4 I1.5
0 Clk - - - Clk - - -
1 Clk - Reset - Clk - Reset -
2 Clk - Reset Start Clk - Reset Start
3 Clk Direction - - Clk Direction - -
4 Clk Direction Reset - Clk Direction Reset -
5 Clk Direction Reset Start Clk Direction Reset Start
6 Clk Up Clk Down - - Clk Up Clk Down - -
7 Clk Up Clk Down Reset - Clk Up Clk Down Reset -
8 Clk Up Clk Down Reset Start Clk Up Clk Down Reset Start
9 Phase A Phase B - - Phase A Phase B - -
10 Phase A Phase B Reset - Phase A Phase B Reset -
11 Phase A Phase B Reset Start Phase A Phase B Reset Start