Environmental conditions
Operation IEC 60721-3-3
Climatic conditions Class 3K5
Mounting location Indoors (weather-protected)
4)
Temperature, general -5...55 °C
Humidity (non-condensing) 5...95 % r.h.
Transportation IEC 60721-3-2
Climatic conditions Class 2K3
Temperature -25...70 °C
Humidity < 95% r.h.
Storage IEC 60721-3-1
Climatic conditions Class 1K3
Temperature -15...55 °C
Humidity 5...95 % r.h.
Max. media temperature when mounted on valve 120 °C
Directives and standards
Product standard EN 60730-x
Electromagnetic compatibility (field of use) For residential, commercial, and industrial environments
EU conformity (CE) CE1T4503xx
5)
RCM conformity AC 230 V 8000078495
5)
EAC compliance Eurasian compliance for all SAV..P..
UL, cUL AC 230 V -
AC / DC 24 V UL 873 http://ul.com/database; file number E35198
Environmental compatibility
Product environmental declarations 71 7331 0522
5)
and A6V101083254
5)
include data on environmentally
friendly product design and testing (RoHS compliance, material composition, packaging, environmental benefits,
disposal).
Dimensions
See Dimensions [ 16]
Accessories
6)
Potentiometer
ASZ7.5/135 0...135 Ω ± 5 %
Voltage DC 10 V
Current rating <4 mA
ASZ7.5/200 0...200 Ω ± 5 %
Voltage DC 10 V
Current rating <4 mA
ASZ7.5/1000 0...1000 Ω ± 5 %
Voltage DC 10 V