Technical data
Power
Operating voltage
SAV31P00 AC 230 V ±15%
SAV61P00..
AC 24 V ± 20 % / DC 24 V +20 % / -15 % (SELV /
PELV)
SAV81P00
Frequency 45...65 Hz
External supply line fusing (EU) Non-renewable fuse 6...10 A slow
Circuit break max. 13 A, tripping characteristic B, C,
D to EN 60898
Power source with current limitation of max. 10 A
Power consumption at 50 Hz
SAV31P00
Stem
retracts/extends
6.5 VA / 4 W
SAV61P00 9.5 VA / 4.5 W
SAV61P/MO 10.2 VA / 5 W
SAV81P00 7 VA / 4.5 W
Typical inrush current
1)
(3-position actuators)
SAV31P00 2.3 A
SAV81P00 4.5 A
Operating data
Positioning times (with the specified nominal stroke) The positioning time may vary depending on the type of
valve
(Type summary [ 3])
SAV31.., SAV61.., SAV81.. 120 s
Positioning force 1100 N
Nominal stroke
On VPF.. DN 100...125 40 mm
On VPF..150 43 mm
Permissible media temperature (valve fitted) 1...120 °C
Signal inputs
Positioning signal ”Y”
SAV31P00, SAV81P00 3-position
SAV31P00
Voltage
AC 230 V ±15%
SAV81P00 AC 24 V ± 20% / DC 24 V + 20% / - 15%
SAV61P00
DC 0...10 V
Power consumption 0.1 mA
Input impedance 100 kΩ
DC 4...20 mA
Power consumption DC 4...20 mA ± 1%
Input impedance 500 kΩ