s SAX.., SAY.. SAX61../MO, SAY61../MO SAV.. SAL.. SAV61../MO Acvatix™ Actuators SAX.., SAY.., SAV.., SAL..
Siemens Switzerland Ltd Smart Infrastructure Global Headquarters Theilerstrasse 1a 6300 Zug Switzerland Tel. +41 58-724 24 24 www.siemens.com/sbt © Siemens Switzerland Ltd, 2010 Subject to change 2 / 87 Siemens Smart Infrastructure Actuators SAX.., SAY.., SAV.., SAL..
Contents 1 About this documentation ...................................................................5 1.1 Navigation / Quick access ......................................................................5 1.2 Revision history .....................................................................................6 1.3 Reference documents ............................................................................7 1.4 1.4.1 1.4.2 1.4.3 1.4.4 Before you start .........................................
3.2.4 Disposal .............................................................................................. 49 4 Functions and control ....................................................................... 50 4.1 4.1.1 3-position control ................................................................................. 50 Combination with RVD.. controller for direct domestic hot water distribution by heat exchanger ............................................................. 52 4.
1 About this documentation 1.1 Navigation / Quick access Information about a specific actuator is provided throughout the document. The structure of chapters 2 to 4 is as follows: Quick access to important information including reference to pages: 2 Engineering Product no. Equipment combinations Accessories SAX31.00 SAX31.03 3 Handling Calibration Accessories 4 Function and control Control Calibration - Page 50-51 - Page 43 Page 53 (mounting) SAX61.03 1) SAX61.03U 1) SAX61.03/MO 1) SAX81.
SAL31.00T10 SAL31.00T20 - SAL31.00T40 Page 50-51 - Page 53 Page 59 Page 50-51 - SAL31.03T10 SAL61.00T10 1) SAL61.00T20 1) SAL61.00T40 1) Page 18 Page 19 Page 43 Page 35-41 Page 71 - 72 SAL61.03T10 1) SAL81.00T10 1) SAL81.00T20 1) - SAL81.00T40 1) SAL81.03T10 1) 1) Note These types of actuator are UL-listed versions Glossary and Index are arranged at the end of the document. 1.2 Revision history Revision First edition 2.0 Date 16.07.2010 2010-12-12 2.1 2011-09-14 3 2012-09-12 3.
1.3 Reference documents Type of document Data Sheet Data Sheet SAX.. SAV.. N4501, N4509, Q4501 Modbus communication profiles N4503, N4510 A6V101037195 Mounting Instructions ASC..: ASZ7.5: AZX61..: ASK39..: ASZ6.6: Mounting Instructions S..6../MO and G..161..
1.4.3 Quality assurance These documents were prepared with great care. · The contents of all documents are checked at regular intervals · All necessary corrections are included in subsequent versions · Anpassungen bzw. Documents are automatically amended as a consequence of modifications and corrections to the products described Please make sure that you are aware of the latest document revision date.
2 Engineering 2.1 Product description The line of large actuators is comprised of stroke actuators SAX.., SAY.., SAV.. and rotary actuators SAL..
2.2 Use SAX.., SAV.. For use in connection with Siemens 2-port or 3-port valves with 20/40 mm stroke, as control or shutoff valves for HVAC plants. SAY.. For the operation of Siemens combi valves of type VPI46.40F9.5Q and VPI46.50F12Q with 15 mm stroke as control valves in ventilation, air conditioning, and district heating systems. SAL.. For use in connection with Siemens butterfly or slipper valves, as control or shutoff valves for HVAC plants.
2.3.2 Product no. Stock no. SAY31P03 S55150-A132 SAY61P03 S55150-A133 SAY61.03U S55150-A135 SAY61P03/MO S55150-A145 SAY81P03 S55150-A134 SAY81.03U S55150-A136 SAX31P03 S55150-A118 SAX61P03 S55150-A114 SAX61P03/MO S55150-A143 SAX81P03 S55150-A116 SAV31P00 S55150-A121 SAV61P00 S55150-A119 SAV61P00/MO S55150-A144 SAV81P00 S55150-A120 Stroke Stock no. SAL31.00T10 SAL31.00T20 SAL31.00T40 SAL31.03T10 SAL61.00T10 SAL61.00T20 SAL61.00T40 SAL61.03T10 SAL81.00T10 SAL81.00T20 SAL81.
2.4 Example Delivery Ordering Product no. SAX81.03 ASZ7.5 Stock no. S55150-A103 S55845-Z106 Description Actuator Potentiometer Quantity 1 1 Actuators, valves and accessories are supplied in individual packs. Type Scope of delivery Device Screws Waveinset - - - - - - SAV../MO - - SAL..T10 - - SAL..T20 2 pcs. M5 x 20 mm 1 pc. 11 mm SAL..T40 2 pcs. M6 x 20 mm 1 pc. 14 mm ASK31N 4 pcs. M6 x 16 mm 1 pc. M5 x 20 mm incl. nut 1 pc. 12 mm 4040U01 SAX.. SAY..P.. SAX../MO, SAY..
ASK33N 4 pcs. M6 x 16 mm 1 pc. M5 x 20 mm incl. nut 1 pc. 12 mm 1 pc. 12 mm ASK35N 2 pcs. M8 x 50 mm 1 pc. M5 x 20 mm incl. nut 1 pc. 12 mm 1 pc. 16 mm 4040U19 16 mm 12 mm 13 / 87 Siemens Smart Infrastructure Actuators SAX.., SAY.., SAV.., SAL..
Valves 2.5.1 Stroke actuators − 3-port valves Stroke actuators SAX.. SAV.. 8) Data Sheet N4501 N4503 Stroke Positioning force Basic Doc. (P4030) Valves PN6 -10…130 °C 4) PN6 -10…130 °C PN10 -10…130 °C 4) PN 10 -10…130 °C PN16 Equipment combinations 4) -10…130 °C 4) PN16 -10…130 °C 4) 20 mm 800 N 40 mm 1600 N SAX.. Δpmax 5) Δpmax [kPa] [kPa] SAV..
Valves -20…130 °C PN25/16 6) Stroke Positioning force Data Sheet N4501 N4503 Basic Doc. (P4030) Valves PN16 -10…130 °C PN16 Stroke actuators SAX.. SAV.. 8) 4) 4) PN25 6) -20…130 °C 4) PN16 -25…130 °C 4) 20 mm 800 N 40 mm 1600 N SAX.. Δpmax Δpmax 5) [kPa] [kPa] SAV.. Δpmax 5) Δpmax [kPa] [kPa] 4040U32 Typical applications · Heating plants · Ventilation and air conditioning plants · Heat generation · Heat distribution · District heating plants Data Sheet Valve type N4403 VXF42.15-..
2.5.2 Stroke actuators − 2-port valves Stroke actuators · Heating plants · Ventilation and air conditioning plants · Heat generation · Heat distribution · District heating plants SAX.. SAV.. 5) Data Sheet N4501 N4503 Stroke Positioning force 20 mm 40°mm 800 N 1600 N 4040U32 Typical applications SAX.. Valves Valves PN6 Basic Doc. (P4030) Data Sheet Valve type N4310 VVF21.22...25 1) 4) VVF21.25-.. 2) 4) VVF21.39..-40 1) 4) VVF21.40-.. 2) 4) VVF21.50 4) VVF21.50-40 4) VVF21.65 4) VVF21.
Stroke actuators · Heating plants · Ventilation and air conditioning plants · Heat generation · Heat distribution · District heating plants SAX.. SAV.. 5) Data Sheet N4501 N4503 Stroke Positioning force 20 mm 40°mm 800 N 1600 N 4040U32 Typical applications SAX.. Valves Valves PN16 Basic Doc. (P4030) Data Sheet Valve type N4403 VVF42.15-.. 2) VVF42.20-6.3 VVF42.25-.. 2) VVF42.32-16 VVF42.40-.. 2) VVF42.50-.. 2) VVF42.65-.. 2) VVF42.80-.. 2) VVF42.100-.. 2) VVF42.125-.. 2) 3) -10…130 °C VVF42.
2.5.3 Stroke Acutuators – combi valves Valves Actuators SAX..P.. Dpmax Dps [kPa] [kPa] SAY..P.. DN PN25 N4855 PN16 N4315 PN25 N4315 Standard flow rate VPI46.40F9.5Q VPI46.50F12Q VPF43.50F16 VPF43.65F24 VPF43.80F35 VPF43.100F70 VPF43.125F110 VPF43.150F160 VPF53.50F16 VPF53.65F24 VPF53.80F35 VPF53.100F70 VPF53.125F110 VPF53.150F160 High flow rate VPF43.50F25 VPF43.65F35 VPF43.80F45 VPF43.100F90 VPF43.125F135 VPF43.150F200 VPF53.50F25 VPF53.65F35 VPF53.80F45 VPF53.100F90 VPF53.125F135 VPF53.150F200 2.
Product no. Stock no. 2.6 Accessories 2.6.1 Electrical accessories Auxiliary switch ASC10.51 Potentiometer ASZ7.5 1) Function module AZX61.1 S55845-Z103 S55845-Z106 S55845-Z107 Max. 2 SAX31.. SAX61.. SAX61.03/MO SAX81.. SAX31P.. SAX61P.. SAX61P03/MO SAX81P.. SAV31.. SAV61.. SAV61.00/MO SAV81.. SAV31P.. SAV61P.. SAV61P00/MO SAV81P.. SAL31.. SAL61.. SAL81.. SAY31P.. SAY61P.. SAY61P03/MO SAY81P.. Notes on ASZ7.5 1) Max. 2 Max. 2 Max. 2 Max. 2 Max. 2 Max. 2 Max. Max. Max. Max. Max. Max. Max.
2.6.2 Mechanical accessories Weather shield ASK39.1 1) Product no. Stock no ASK31N for VBF21.. S55845-Z109 S55845-Z100 Max. 1 - SAY.. SAX.. SAV.. SAL.. SAL..T10 SAL..T20 SAL..T40 DN 65…150 Max. 1 Mounting set ASK32N for ASK33N for VBI31.. 2) VKF41.. VBF21.. VCI31.. 2) VBG31.. 2) S55845-Z211 S55845-Z101 - P - - P DN 150…200 DN 40…65 DN 80...200 1) SA..61../MO are not suitable for outdoor applications. 2) Types VBI31.., VCI31.., and VBG31..
2.7.2 Rotary actuators SQL.. to SAL.. SQL.. SQL31.. SQL32.. SQL33.. SQL83.. SQL35.. SQL85.. SAL.. SQL31.10 SQL32.10 SQL32.12 Pos. time [s] 120 125 70 Torque [Nm] 12,5 12,5 12,5 SQL32.13 SQL33.00 SQL33.03 SQL83.00 SQL83.04 SQL35.00 SQL35.00 SQL85.00 SQL85.00 30 125 30 125 30 125 125 125 125 5 12,5 10 12,5 10 20 20 20 20 VBF31.. B3f.. C1f.. K1i.. K1f.. VKF41.. VKF45..
Stroke actuators ASZ6.5 ASZ7.4 ASC9.4 ASC9.5 Stem heater 1 auxiliary switch, 1 potentiometer (1000 Ω) Double auxiliary switch Auxiliary switch SQX31.. SQX81.. ASZ6.5 SQX.. SQX61.. SQX32.. SQX82.. ASZ6.5 ASZ6.5 SQX62.. ASZ6.5 ASZ6.6 SAX61.. ASZ6.6 ASZ7.4 - ASZ7.4 - ASC10.51 + ASZ7.5 - ASC9.4 ASC9.5 - ASC9.4 ASC9.5 - 2x ASC10.51 ASC10.51 - Rotary actuators SQL.. SQL32.. SQL33.. SQL83.. - SQL31.. ASZ7.4 ASC9.4 ASC9.5 ASZ8.4 ASZ9.4 ASC1.
2.9 Sizing 2.9.1 Parallel operation of actuators SA..31.. and SA..81.. 3-position actuators must have one specific controller each, refer to "Connection diagrams" (page 78). SA..61.. Up to 10 actuators can drive in parallel on a controller output with a rating of 1 mA. Modulating actuators have an input impedance of 100 kΩ. SA..61../MO The Modbus converter is designed for analog control on 0..10 V on the actuator side.
The following diagram can be used to determine the cable lengths and wire crosssectional areas. Cable length L L/P-diagram for AC/DC 24 V Power Consumption P Permissible cable length L as a function of power P and cross-sectional area of wire as a parameter Note Formulas for wire lengths P is the decisive power consumption of all actuators connected in parallel. When operating on AC 24 V, power consumption is in VA; when operating on DC 24 V, in W.
3 Handling 3.1 Mounting and installation 3.1.1 Mounting positions Outdoor use 1) 2) Indoor use 1) Only in connection with weather shield ASK39.1 2) SA..61../MO are not suitable for outdoor applications. 3.1.2 Fitting stroke actuators to seat valves VVF.. / VXF.. or VVG.. / VXG.. First, observe "Mounting positions" (page 25). Caution! Risk of burns from hot surfaces! If you touch heated parts, you will get burns as result. · Allow to cool parts. · Wear protective gloves.
5 10 mm 7 3.1.3 6 8 10 mm Avoid missalignement on V_G41 valves with fittings Caution! Risk of burns from hot surfaces! If you touch heated parts, you will get burns as result. · Allow to cool parts. · Wear protective gloves. 1 2 On threaded valves it’s possible that the actuator is missaligned on the valve due to a collision with the fitting. If so, please take care for correct mounting, either by turning the actuator or by adjusting the fitting (e.g.
3.1.4 Fitting rotary actuators to butterfly valves VKF41.. First, observe "Mounting positions" (page 25). Mounting set ASK33N Scope of delivery Mounting set (2 parts) 1 adapter inc. fixing screw 5 screws 1 adapter 4 pcs. M6 x 16 mm 1 pc. M5 x 20 incl. nut Note Actuators SAL.. are not compatible with mounting sets ASK31, ASK32, ASK33, ASK35, ASK40, and ASK41. Caution! Risk of burns from hot surfaces! If you touch heated parts, you will get burns as result. · Allow to cool parts.
4 12 mm 6 5 5 mm 7 4 mm 1) 1) Angle position errors between actuator shaft and valve stem must be corrected via manual control (refer to "Manual adjuster" page 69). 28 / 87 Siemens Smart Infrastructure Actuators SAX.., SAY.., SAV.., SAL..
3.1.5 Fitting rotary actuators to slipper valves VBF21.. First, observe "Mounting positions" (page 25). Scope of delivery Mounting set ASK31N Mounting set (2 parts) 1 adapter inc. fixing screw 5 screws 1 adapter 4 pcs. M6 x 16 mm 1 pc. M5 x 20 mm incl. nut Mounting set ASK32N for VBF21.., DN 40…50 Mounting set (2 parts) 5 screws 4 pcs. M6 x 16 mm 1 pc. M5 x 20 mm incl. nut 1 adapter With VBF21.. (e.g. DN 125), the following steps must be performed prior to fitting the mounting set.
Opening counterclockwise 3.1a 4 mm, 5 mm 3.1b ASK31N 12 mm ASK32N 3.2a 4 mm, 5 mm 3.2b ASK31N 12 mm ASK32N 4 mm, 5 mm 4 mm, 5 mm 30 / 87 Siemens Smart Infrastructure Actuators SAX.., SAY.., SAV.., SAL..
Opening clockwise 3.3a 4 mm, 5 mm 3.3b ASK31N 12 mm ASK32N 3.4a 4 mm, 5 mm 3.4b ASK31N 12 mm ASK32N 4 mm, 5 mm 4 mm, 5 mm For further mounting positions of VBF 21.. and routing of the connection cables the rotary actuators and adapters must be mounted according to the sketches above. 31 / 87 Siemens Smart Infrastructure Actuators SAX.., SAY.., SAV.., SAL..
3.1.6 Fitting rotary actuators to butterfly valves VKF46.. First, observe "Mounting positions" (page 25). Standard scope of delivery VKF46.. Product no. Scope of delivery 2 screws 1 dapter SAL..T20 2 pcs. M5 x 20 mm 1 pc. 11 mm SAL..T40 2 pcs. M6 x 20 mm 1 pc. 14 mm Caution! Risk of burns from hot surfaces! If you touch heated parts, you will get burns as result. · Allow to cool parts. · Wear protective gloves.
3.1.7 Fitting rotary actuators to butterfly valves VKF45.. First, observe "Mounting positions" (page 25). Mounting set ASK35N For VKF45.. Mounting set (2 parts) Scope of delivery 5 screws 2 adapters 4040U15 4040U19 2 pcs. M8 x 50 mm 1 pc. M5 x 20 mm incl. nut Note 1 pc. 12 mm 1 pc. 16 mm 16 mm 12 mm Actuators SAL.. are not suited for use with mounting sets ASK31, ASK32, ASK33, ASK35, ASK40, and ASK41.
4 4 mm 4040J52 3 6 6 mm 4040J55 5 34 / 87 Siemens Smart Infrastructure Actuators SAX.., SAY.., SAV.., SAL..
3.1.8 Before fitting the accessory items shown below, the following steps must be performed: SA..31.. Danger! Danger to life from electrical current! There is an immediate risk of fatal injury in case of contact with live parts of SA..31... · Disconnect actuator from power. 1. 2. 3. 4. 5. 6. Actuator is mechanically connected to a Siemens valve. Observe compatibility and choice of combinations. Refer to "Accessories" (page 19). Disconnect actuator from power.
Potentiometer ASZ7.5 1 potentiometer ASZ7.5 Scope of delivery 1 screw 2 screw covers 1 pc. First, observe "Special notes on mounting" (page 35). Also observe "Notes on ASZ7.5" (page 19). Danger! Danger to life from electrical current! If a live wire gets in contact with the screws the whole actuator housing is a live. · Fit the screw covers first. Plug-in space A 1 2 3 4 No.: 1 5 4040J73 Turn to 0% 36 / 87 Siemens Smart Infrastructure Actuators SAX.., SAY.., SAV.., SAL..
6 7 Function module AZX61.1 No.: 2 Observe "Wiring" (page 41) 8 Observe " Connection terminals" (page 77) First, observe "Special notes on mounting” (page 35). 1 Set function module (page 54) 2 Nr.: 3 Plug-in space B 3 4 37 / 87 Siemens Smart Infrastructure Actuators SAX.., SAY.., SAV.., SAL..
Auxiliary switch ASC10.51 1 auxiliary switch ASC10.51 Scope of delivery 1 screw 2 screw covers 1 pc. First, observe "Special notes on mounting" (page 35). Danger! Danger to life from electrical current! If a live wire gets in contact with the screws the whole actuator housing is a live. · Fit the screw covers first. Plug-in space A 1 2 3 4 5 No.: 1 Adjust switch position (refer also to "Manual operation" page 69) 38 / 87 Siemens Smart Infrastructure Actuators SAX.., SAY.., SAV.., SAL..
6 No.:1 When initial situation: 0 Ω 7 Observe "Wiring" (page 41) When initial situation: ∞ Ω 8 Observe "Connection terminals" (page 77) First, observe "Special notes on mounting" (page 35). Danger! Danger to life from electrical current! If a live wire gets in contact with the screws the whole actuator housing is a live. · Fit the screw covers first. Plug-in space B 1 2 3 4 No.: 1 39 / 87 Siemens Smart Infrastructure Actuators SAX.., SAY.., SAV.., SAL..
5 Adjust switch position (refer also to "Manual operation" page 69) 6 No.: 1 When initial situation: 0 Ω 7 Stem heating element ASZ6.6 When initial situation: ∞ Ω 8 Observe "Wiring" (page 41) Observe "Connection terminals" (page 77) Scope of delivery 1 stem heating element ASZ6.6 1 screw 1 pc. M4 x 30 incl. nut When fitting the stem heating element, stroke actuator and valve must be assembled. The stem heating element is powered separately. First, observe "Special notes on mounting” (page 35).
Weather shield ASK39.1 First, observe "Special notes on mounting” (page 35). Scope of delivery Weather shield ASK39.1 Notes 2 UV-proof cable ties · To protect the actuator when used outdoors, the weather shield must always be fitted. · If fitted several times, 2 UV-proof cable ties (800 x 4 mm) must be used. · The manual adjuster cannot be used when the weather shield is mounted. · SA..61../MO are not suitable for outdoor applications. 1 2 4040J31a 4040J30a 3.1.
Prior to installation, the following preconditions must be satisfied: · Actuator is mechanically connected to a Siemens valve. · Housing cover is removed (step 6 "Special notes on mounting", page 35). Communicating actuators 1 2 No.: 4 4040J42 Actuator Device contains fixed connecting cable. Left cable duct used (A). 3 4 Observe " Connection terminals" (page 77) 4040J78 G 1 4040J79 3 4 Observe " Connection terminals" (page 77). Observe "Notes on ASZ7.5" (page 19).
Mechanically 3.2 Commissioning and operation 3.2.1 Function check and Calibration Before making the function check, the following preconditions must be satisfied: · Environmental conditions specified in chapter "Technical data" (page 73) · Actuator is mechanically connected to a Siemens valve · Actuator is in "Manual operation" mode (page 69). The actuator can be operated with the help of the "Manual adjuster" (see page 69).
Make the function check for modulating actuators after the calibration with a point test according to the following table: SAX61.03/03U, SAV61.00/00U and SAL61..
Auxiliary switch ASC10.
3.2.2 Commissioning Modbus RTU The devices were developed specifically for use with Climatix push-button configuration as described in document CE1A3975 1). As an alternative, the bus can be configured via the local HMI; see Section User interface, pg. 47. Check the following during commissioning: · Bus configuration (address, baud rate, type of transmission and optional termination).
User interface Pushbutton operation Action Pushbutton operation Feedback message Current Modbus address Button pressure < 1s 1st digit: red (starting from lowest address position) 2nd digit: green 3rd digit: orange The LED blinks blue once after address indication and when bus termination is On Example: 124 = 4x red, 2x green, 1x orange Switches bus termination On/Off Switch-on 1. Press button 3x Blinking or flickering of LED stops (termination mode) 2.
Reset actuator with pushbutton Enter address using pushbutton 1. 2. 3. 4. Press button >10s à LED blinking orange Release button while blinking à LED blinking for another 3s Reset is interrupted if the pushbutton is pressed during the 3s After 3s, à LED is lit red (reset) while the device restarts. The Modbus address can be set without extra tool by means of pushbutton addressing. To display the current Modbus address, press the button <1s.
Set address "50": 1. Enable addressing mode 2. Skip over 1st digit: Press button until LED is green – release button 3. Enter the 2nd digit: Press button 5x à LED blinks green each time the button is pressed 4. Save address (skip 3rd digit): Press button until LED is red – release button à The address is saved and displayed 1x for confirmation Set address "5": 1. Enable addressing mode 2.
4 Functions and control 4.1 3-position control A 3-position signal drives the actuator via connection terminals Y1 or Y2. The required position is transferred to the valve.
The specified positioning times refer to the respective nominal stroke / nominal angular rotation. Since the end positions of rotary actuators are inside the actuator, the following remarks refer to stroke actuators. The resulting effective strokes vary, depending on the type of valve, resulting in shorter or longer actuator positioning times. Stroke of valve-actuator combination [mm] Positioning times stroke model Positioning time [sec] Legend diagram A B A…B Notes Mechanical end position in SAX..
Notes 4.1.1 Combination with RVD.. controller for direct domestic hot water distribution by heat exchanger The design based slow reaction on control signals of SAX31.., SAX81.., SAV31.., SAV81.., SAY31.., SAY81.., SAL31.. und SAL81.. actuators doesn’t allow the actuator to react on very short control pulses. Only control pulses with a length greater than 300 ms allow a sufficient reaction. Especially the direct domestic hot water control does not allow such long control pulses.
4.2 Modulating control The modulating positioning signal drives the actuator steplessly. The positioning signal range (DC 0...10 V / DC 4...20 mA, 0...1000 Ω) corresponds in a linear manner to the positioning range (fully closed...fully open, or 0…100 % stroke).
4.3 DIL switches Function module AZX61.1 Acting direction Sequence control OFF 1) Direct acting positioning signal Y or Z Sequence control not active ON 1) Reverse acting positioning signal Y or Z Sequence control (signal adaptation) 1) Factory setting: All switches set to OFF The function module may not be used in combination with SA..61../MO. 4.3.
Examples Legend diagram A B C H 4.3.
4.4 DIL switches Positioning signal and flow characteristic selection Positioning signal "Y" 1) Position feedback "U" Flow characteristic OFF 1) DC 0…10 V DC 0…10 V log = equalpercentage ON DC 4…20 mA DC 0…10 V lin = linear Factory setting: All DIL switches set to OFF Ω Flow characteristic SAX61.03 / SAV61.00 with VVF.. Actuator Valve VVF.. / VVG41.. Totally Actuator Combi-Valve VPF43/VPF53 Totally log lin Flow characteristic SAY61P03 / SAX61P03 / SAV61P00 with VPF..
4.5 Acting direction and flow characteristic The selection of changeover of acting direction and characteristic with the DIL switches of the function module AZX61.1 depends on the type of actuator (with or without fail safe function) and the associated type of valve (valve characteristic, push to open, pull to open). When the positioning signal increases (DC 0…10 V, DC 4…20 mA, 0...
Actuator Positioning signal Y, Z Actuator Position feedback U Direct acting Reverse acting Y, Z H U 4.7 Positioning signal Stroke Position feedback Acting direction: direct Acting direction: reverse Position control with ClosedPositionSynchronization Within SAX/SAV/SAL61/SAY61.. actuators the position control works based on the HALL-sensor pulses from the brushless DC-motor calculating with an internal stroke model calculating the actual position.
After synchronization the actuator follows the control signal again. 4.7.1.1 Active forced position input on Z If after return to automatic mode a signal on Z is active (GND, AC/DC 24 V or 0…1000 Ohm) the ClosedPosition-Synchronization is deactivated as long as the signal on Z remains. After Z is deactivated the ClosedPosition-Synchronization will be performed. Note ClosedPosition-Synchronization is only automatically activated after manual operation.
Note · Observe status indication (actuator LED) during and after calibration (page 70). · If the actuator does not detect the second end position within an appropriate stroke range (SAX.., SAY.. max. 25 mm; SAV.. max. 45 mm), the first end stop will be adopted and the actuator operates with a working range of 20 mm, respectively 40 mm. 4.9 Signal priorities The actuators are controlled via different interlinked positioning signal paths (positioning signal “Y“, forced control input “Z“, manual adjuster).
Example The supposed position is 50%, Y = 2 V, the actuator travels 30% of the stored valve stroke in the direction of "Actuator’s stem retracted". If the actuator reaches the seat within this 30% travel, it interprets the position as "Valve fully closed" and shifts the position of the valve’s stroke accordingly without changing the extent of travel. From now on, the actuator follows the changed valve stroke position.
4.12 SA..61.. only Forced control Z Forced control is affected by changeover of acting direction.
After a power failure, valve seat identification is not active – the actuators without fail safe function define their stroke position upon return of power at 50% and automatically set their internal setpoint in register 1 to the startup setpoint (register 516). The actuator closes at this setting. There is a short-term deviation between the setpoint and the internal stroke position. When the valve plug reaches each seat for the first time, the actuator readjusts its stroke mode.
Calibration takes place in the following phases: · Actuator drives to H0 (1), valve closes. Detection of upper end position. · Actuator drives to H100 (2), valve opens. Detection of lower end position. · The detected values are stored (3). Then the actuator follows the positioning signal. · If the actuator does not detect the second end position within an appropriate stroke range (max. 25 mm), the first end stop will be adopted and the actuator operates with a working range of 20 mm.
Parameters 259 Op mode R 1 = POS 260 MinPosition R 0…100% = 0…10000 0% 261 MaxPosition R 0…100% = 0…10000 100% 262 Actuator runtime R 30s 30s 263 Positioning signal characteristic between Y and U R 0 = Linear (e.g. SAX61..
Communication properties Communication Communications protocol Modbus RTU RS-485, not galvanically separated Number of nodes Max. 32 Address range 1...
· If clogging/a blockade occurs during the self test, the test is failed, even if the device clears it within 3 tries. Register 256 “Reset” The actuator supports the following re-initialization / reset behaviour: · Local reset by push-button · Remote reset: Using “Remote-Reset” command. Effect of reset: · Process values except actual value and setpoint: set to ex-works default values.
Register 769 “Status” Status Bit 00 1 = Not available Bit 06 1 = Not available Bit 01 1 = Backup mode active Bit 07 1 = Not available Bit 02 1 = Not available Bit 08 1 = Not available Bit 03 1 = Not available Bit 09 1 = Self test failed Bit 04 1 = Mechanical error, device blocked, Bit 10 1 = Self test successful Bit 11 1 = Not available manual intervention1) or calibration1) Bit 05 1) 1 = Not available After 10 seconds 4.14 Technical and mechanical design 4.14.
4.14.2 Coupling SAX.., SAV.. The stem coupling (1) and neck coupling (2) ensures full backward compatibility with all types of Siemens large-stroke valves produced since 1975. SAL.. Mounting sets are available for use with butterfly and slipper valves. 4.14.3 Manual adjuster Automatic When the motor drives the manual adjuster turns. Thus in automatic mode, the manual adjuster is used for indication of travel.
4.14.4 Indicators A Indication of travel B Scale C Indicator D LED Status indication Position indication Operational status indication In Automatic mode, the manual adjuster serves for the indication of travel. See "Automatic" (page 69). Position indication Position indication is on 2 opposite sides. When turning the manual adjuster, the indicator moves in the same direction. The scale indicates the stroke. When reaching the stops, the valve is either fully open or fully closed.
4.14.5 Electrical accessories Auxiliary switch ASC10.51 The auxiliary switch ASC10.51 switches on or off when a certain position is reached. The switching point can be set between 0…100%. AC 24 V...230 V / 6 (2) A S1 Switching point for S1–S2 and S1–S3 cannot be set separately. If S1–S2 is open then S1–S3 is closed. S3 S2 Adjustable switching point Application example: Potentiometer ASZ7.5/.. Potentiometer ASZ7.
Function module AZX61.1 Function module AZX61.1 offers the following choices for changing control: · Changeover of acting direction (page 55) · Sequence control (page 54) Stem heating element ASZ6.6 Stem heating element ASZ6.6 prevents the formation of ice on the stem when medium temperatures drop below 0 °C. It is suited for universal use with valves having a stem diameter of 10 or 14 mm. The stem heating element heats up to 85 °C.
5 Technical data SAY.. Power supply SAX.. SAV.. SAL.. Operating voltage SA..31.. SA..61.. SA..81.. AC 230 V ± 15 % AC 24 V ± 20 % / DC 24 V + 20 % / -15 % (SELV) AC 24 V ± 20 % / DC 24 V + 20 % / -15 % (SELV) Frequenz 45…65Hz External supply line protection (EU) · · · 6 A...10 A slow Circuit breaker max. 13 A Characteristic B, C, D according to EN 60898 Power source with current limitation of max. 10 A Power consumption at 50 Hz SAX31.00 Stem retracts / extends 3.5 VA / 2 W SAX31.
SAY.. Function data Positioning times with specified nominal stroke / nominal angular rotation SAX..00, SAV.., SAL..00 Communi cation 120 s 120 s 30 s - 30 s Positioning force Torque SAL..T10 SAL..T20 2) SAL..T40 2) Nominal stroke Angular rotation 200 N 800 N 20 mm - 1600 N 40 mm - 10 Nm running 20 Nm running 40 Nm running 90° Positioning signal ”Y” SA..31.., SA..81.. SA..31.. Voltage SA..81.. Voltage SA..61.. (DC 0...10 V) Current draw Input impedance SA..61.. (DC 4...
SAY.. Environmental conditions Operation Climatic conditions Mounting location Temperature General -15…55 °C Humidity (noncondensing) 5…95 % r.h. Transport Climatic conditions Temperature Humidity SAX.. IEC 60721-3-3 Class 3K5 Indoors (weather-protected) IEC 60721-3-1 Class 1K3 -15…55 °C 5…95 % r.h. Product standard Electromagnetic compatibility (Application) EU Conformity (CE) EN60730-x For residential, commercial and industrial environments UL, cUL AC 230 V 130 °C 130 °C 7) 130 °C SAX..
6 Connection diagrams and dimensions 6.1 Internal diagrams SA..31.. A Accessories and / or B 1x ASC10.51 AC 24 V...230 V / 6 (2) A S1 1x ASC10.51 AC 24 V...230 V / 6 (2) A S1 S3 S2 or 1 x ASZ7.5 S3 S2 SA..61.. SA..61../MO A AC 24 V / DC 24 V SA..81.. Accessories and / or B 1x ASC10.51 1x ASC10.51 AC 24 V...230 V / 6 (2) A AC 24 V...230 V / 6 (2) A S1 S1 S3 S2 S3 S2 A Accessories and / or B 1x ASC10.51 1x ASC10.51 AC 24 V...230 V / 6 (2) A AC 24 V...
SA..31.. 6.2 Connection terminals 6.2.1 Actuators AC 230 V, 3-position System neutral (SN) Positioning signal (actuator’s stem extends / actuator’s spindle turns clockwise) Positioning signal (actuator’s stem retracts / actuator’s spindle turns counter-clockwise) SA..61.. AC/DC 24 V, DC 0…10 V / 4…20 mA / 0…1000 Ω Sytem neutral (SN) System potential (SP) Positioning signal for DC 0…10 V / 4…20 mA Measuring neutral Position feedback DC 0...
6.3 SA..31.. Connection diagrams AC 230 V L L Y1 Y2 N A L N N1 Y1, Y2 N1 Actuator Phase Neutral Controller Positioning signals N SA..61.. A F2 F3 F4 M N1 SN SP U Y Z Actuator Frost protection thermostat; terminals: 1 – 2 frost hazard / sensor is interrupted (thermostat closes with frost) 1 – 3 normal operation Temperature detector Frost protection monitor with 0…1000 Ω signal output, does NOT support QAF21.. or QAF61..
SA..81.. SA..81.. AC/DC 24 V 4041G10b SP A N1 SN SP Y1, Y2 Y1 Y2 Actuator Controller System neutral System potential AC/DC 24 V Positioning signals G G0 N1 SN 79 / 87 Siemens Smart Infrastructure Actuators SAX.., SAY.., SAV.., SAL..
6.4 Dimensions 6.4.1 Stroke actuators B C1 C2 M25 4040M01_02 A M20 E 1 2 Type SAX.. (U1)) SAX../MO 3) Mit ASK39.1 SAX../SAV..: SAX..U/SAV..U: SAX../SAV..: SAX..U/SAV..U: M25 ½" (Ø 21.5 mm) M20 ½" (Ø 21.5 mm) A B C C1 C2 D E ► ►► 242 124 150 68 82 80 100 100 200 +25 154 300 200 100 - - - - 265 124 150 68 82 80 100 100 200 +25 154 300 200 100 - - - - 242 124 150 68 82 80 100 100 200 1) SAV.. (U ) SAV../MO Mit ASK39.1 1) SAY.. (U ) SAY..
External Modbus converter A6V101006034M01 6.4.2 Type SA../MO 1) X [mm] [kg] 250 0.15 1) Already included in total weight Dimensions in mm 81 / 87 Siemens Smart Infrastructure Actuators SAX.., SAY.., SAV.., SAL..
6.4.3 Rotary actuators B C1 C2 H G F A 1 D 1 2 Typ E M8 M6 M5 4040M02 2 SAL..: M25 SAL..: M20 A B C C1 C2 D E F G H ► ►► SAL..T10 SAL..T20 SAL..T40 SAL.. 160 124 150 68 82 82 88 42 50 70 100 200 1.475 1.600 1.625 With ASK39.1 +25 154 300 200 100 - - - - - - - 1.710 1.835 1.860 With mounting set ASK3..N Type A1 D1 E1 E2 SAL.. with ASK3..N 188 88 80 44 With ASK39.
7 Revision numbers Product no. SAX31.00 SAX31.03 SAX31P03 SAX81.00 SAX81.03 SAX81.03U SAX81P03 SAX61.03 SAX61.03U SAX61P03 SAX61.03/MO SAX61P03/MO Valid from rev. no. ..H ..H ..H ..H ..H ..H ..H ..H ..H ..H ..H ..A SAV31.00 SAV61.00 SAV61.00U SAV61P00 SAV81.00 SAV81.00U SAV81P00 SAV61.00/MO SAV61P00/MO ..B ..B ..B ..B ..B ..B ..B ..A ..A Product no. SAL31.00T10 SAL31.00T20 SAL31.00T40 SAL31.03T10 SAL61.00T10 SAL61.00T20 SAL81.00T40 SAL61.03T10 SAL81.00T10 SAL81.00T20 SAL81.00T40 SAL81.
8 Glossary 8.1 Symbols Caution, general danger – read the notes! Caution, hot surface – read the notes! Condition as supplied to costumer Crosstip screwdriver (Pozidriv) Slotted screwdriver Screw wrench Allen key 8.2 Terms Climatix TM The complete product range of flexible and scalable control solutions, standardized up to and including freely programmable solutions. Specialized for HVAC applications.
Index 3-position control ................................................ 50 A/D conversion ............................................. 50, 53 About this documentation...................................... 5 Accessories .................................................. 19, 75 Electrical accessories ...................................... 19 Mechanical accessories ................................... 20 Acting direction ............................................. 55, 57 Angular rotation ..................
Manual adjustment ..................................50, 53, 64 Mechanical accessories ...................................... 72 Modbus RTU ...................................................... 46 Modulating control .............................................. 53 Montagesatz ASK3..N ......................................... 18 Montagesatz ASK31N ................................... 20, 29 Montagesatz ASK33N ......................................... 20 Montagesatz ASK35N ....................................
Issued by Siemens Switzerland Ltd Smart Infrastructure Global Headquarters Theilerstrasse 1a 6300 Zug Switzerland Tel. +41 58-724 24 24 www.siemens.com/sbt © Siemens Switzerland Ltd, 2010 Technical specifications and availability subject to change without notice Frei verwendbar Siemens Building Technologies 87 / 87 Actuators SAX.., SAY.., SAV.., SAL..