Operating instructions
PROFINET IO functionality
7.1 Configuring with PROFINET IO
Industrial Ethernet SCALANCE X-100 and SCALANCE X-200 Product Line
7-2 Operating instructions, 09/2006, A5E00349864 Release 7
Including the SCALANCE X-200
To include the individual switches as PN IO devices, the devices of the SCALANCE X-200
product line must exist in the module catalog under PROFINET IO.
Procedure
If the devices are not yet included in STEP 7, follow the steps below:
1. In the dialog, select HW Config -> Options "Install GSD files".
The following dialog opens:
Figure 7-2 Installing PNIO GSD Files
2. Use the browse function to locate the supplied xml file (for example gsdml-v1.0-Siemens-
SCALANCE_X_2xx-20040729.xml).
3. Then adopt the file using the "Install" function.
The devices of the SCALANCE X-200 product line are now included in the module
catalog (refer to the module catalog in the following figure).
4. Drag the required SCALANCE X-200 from the hardware catalog, here, for example
SCALANCE X208 - PROFINET IO > General> SCALANCE X-200 Switches>
SCALANCE X-208 to the PROFINET IO system.