PROFINET IO functionality
7.3 Access options with PNIO
Industrial Ethernet SCALANCE X-100 and SCALANCE X-200 Product Line
Operating instructions, 09/2006, A5E00349864 Release 7
7-13
Enable_alarms:
This bit list specifies what is to be monitored. If a bit is set, this alarm source is enabled.
Reserved
Bit 4 - 31
Enhanced_Alarm_Mode
Bit 3
Reserved
Bit 2
C-PLUG
Bit 1
Red_power
Bit 0
0 0:No button actuation
Settings from data
record 200 are relevant
0 0: No C-PLUG
monitoring
0: No monitoring of the
redundant power supply
1: Button actuation, see
"Defining the desired
alarm generation
response"
1: Missing or
incorrect C-
PLUG generates
alarm
1: Monitoring of the
redundant power supply
Enhanced_Alarm_Mode:
If this bit is set to 1, the following alarm setpoints are frozen by the state on button actuation:
• Ports: LinkStatus.
• C-PLUG: Monitor C-PLUG.
• RED_Power: Monitor redundant power supply.
In this case, bits 0 and 1 must be ignored by the module.
For all connections (ports, C-PLUG. Red-Power) a deviation of the actual state from this
frozen state results in an alarm being generated. The response set with data record 200 is
ignored.
Note
This data record can also be read if the device is not in data transfer mode (PG access). It
supplies the current alarm setting for this port. This means that the current state can be
reread for diagnostics purposes. This is necessary because the alarm property can be
configured using the second parameterization option (button actuation). Bits 0,1, and 3 must
be set accordingly.
Data record 5:
Supplies the current alarm setting for this port
Access: Read-only
typedef struct {
Word BlockType;
Word BlockLength;
Byte BlockVersionHigh;