Operating instructions
PROFINET IO functionality
7.3 Access options with PNIO
Industrial Ethernet SCALANCE X-100 and SCALANCE X-200 Product Line
7-14 Operating instructions, 09/2006, A5E00349864 Release 7
Byte BlockVersionLow;
DWord status; };
BlockType:
1: Constant
BlockLength:
6: Constant in device data, designates the length without Type+ Length
BlockVersionHigh:
1: Constant in device data, designates the major version
BlockVersionLow:
1: Constant in device data, designates the minor version
Status:
Reserved
Bits 8-31
C-PLUG_status
Bits 4-7
Reserved
Bits 2-3
Fault_line_status
Bit 1
Power line redundancy
Bit 0
0 Information regarding
the configuration plug
of the network
component
0: C-PLUG inserted
and ok
1:C-PLUG not inserted
2: C-PLUG inserted but
not ok (incorrect type)
3: C-PLUG inserted but
not ok (checksum error)
Information
regarding the
current state of
the signaling
contact
0: Fault line
passive
1: Fault line
active
This bit provides
information about the
redundant power supply
0: not redundant
1: redundant
Note
This data record can also be read if the device is not in data transfer mode (PG access).
This means that the current state can be reread for diagnostics purposes.
Data record 200:
This data record defines the alarm response of a port.