Data Sheet for Product
s Industry, Inc.
Building Technologies Division
Specifications
– Speaker appliances are Siemens Series ‘SE’ Speakers, and the speaker-strobe appliances
are Siemens Series ‘SE’ Speaker Strobes or approved equals
– Speakers are UL Listed under Standard 1480 for Fire Protective Service, and speakers
equipped with strobes are listed under
UL Standard 1971 for Emergency Devices
for the Hearing-Impaired
– Siemens Series ‘SE’ wall-mount appliances each have a listed sound output of up to
89 dBA at 10 feet (3 meters) and a listed frequency response of 400 to 4,000 Hz
– All ceiling-mount models have listed sound output of up to 87 dB at 10 feet (3 meters)
and a listed frequency response of 400 to 4,000 Hz
– Speaker portion is designed for a field-selectable input of either 25 or 70 VRMS;
with selectable power taps from 1/8 Watt to 2 Watts
– Speakers are comprised of a sealed-back construction
– All inputs accept terminals that use
#
12 to
#
18 AWG wire sizes
– Strobe intensity, where multi-Candela appliances are specified, have
field-selectable settings, and are rated per
UL Standard 1971 for:
15/30/75/110cd (wall mount)
135/185cd (wall mount, high Candela)
15/30/75/95cd (ceiling mount)
115/177cd (ceiling mount, high Candela)
– Manual selector switch for setting the candela is tamper-resistant
– The strobe portion, when synchronization is required, is compatible via the use of the Siemens
50-point, 252-point and 504-point addressable fire alarm control panels (FACPs), as well as with:
FireFinder® XLS/V FACPs
PAD-3 or PAD-4™ NAC Extenders
Siemens dual-sync control (DSC) modules
– The strobes do not drift out of synchronization at any time during operation
– The strobes will revert to a non-synchronized flash-rate, if the sync module
or Power Supply should fail to operate (i.e.
– contacts remain closed)
– Wall-mount speaker and speaker-strobe appliances are designed for indoor-flush
mounting to 4” (10.2 cm.) square –x– 2-1/8” (5.4 cm.) electrical boxes without
need for an extension ring or surface mounting
– Ceiling-mount, speaker-strobe Series ‘SE’ appliances are designed for indoor, flush mounting
– Speaker and speaker-strobe incorporate a speaker-mounting plate with a snap-on grille cover
The finish on each grille for Siemens Series ‘SE’ speakers and speaker-strobes is white or red
– All speaker and speaker-strobe appliances are listed for Special Applications:
Strobes are designed to flash at 1-flash-per-second minimum over their “Regulated Input Voltage Range”
Notes: NFPA-72 specifies a flash rate of 1-to-2 flashes per second.
ADA Guidelines specify a flash rate of 1-to-3 flashes per second.
All candela ratings represent minimum-effective Strobe intensity, based on UL Standard 1971