Specifications
Speaker appliances are Siemens Series ‘SESpeakers, and the speaker-strobe appliances
are Siemens Series ‘SE Speaker Strobes or approved equals
Speakers are UL Listed under Standard 1480 for Fire Protective Service, and speakers
equipped with strobes are listed under
UL Standard 1971 for Emergency Devices
for the Hearing-Impaired
Siemens Series ‘SE’ wall-mount appliances each have a listed sound output of up to
89 dBA at 10 feet (3 meters) and a listed frequency response of 400 to 4,000 Hz
All ceiling-mount models have listed sound output of up to 87 dB at 10 feet (3 meters)
and a listed frequency response of 400 to 4,000 Hz
Speaker portion is designed for a field-selectable input of either 25 or 70 VRMS;
with selectable power taps from 1/8 Watt to 2 Watts
Speakers are comprised of a sealed-back construction
All inputs accept terminals that use
#
12 to
#
18 AWG wire sizes
Strobe intensity, where multi-Candela appliances are specified, have
field-selectable settings, and are rated per
UL Standard 1971 for:
15/30/75/110cd (wall mount)
135/185cd (wall mount, high Candela)
15/30/75/95cd (ceiling mount)
115/177cd (ceiling mount, high Candela)
Manual selector switch for setting the candela is tamper-resistant
The strobe portion, when synchronization is required, is compatible via the use of the Siemens
50-point, 252-point and 504-point addressable fire alarm control panels (FACPs), as well as with:
FireFinder® XLS/V FACPs
PAD-3 or PAD-4™ NAC Extenders
Siemens dual-sync control (DSC) modules
The strobes do not drift out of synchronization at any time during operation
The strobes will revert to a non-synchronized flash-rate, if the sync module
or Power Supply should fail to operate (i.e.
contacts remain closed)
Wall-mount speaker and speaker-strobe appliances are designed for indoor-flush
mounting to 4” (10.2 cm.) square x 2-1/8” (5.4 cm.) electrical boxes without
need for an extension ring or surface mounting
Ceiling-mount, speaker-strobe Series ‘SE appliances are designed for indoor, flush mounting
Speaker and speaker-strobe incorporate a speaker-mounting plate with a snap-on grille cover
The finish on each grille for Siemens Series ‘SE speakers and speaker-strobes is white or red
All speaker and speaker-strobe appliances are listed for Special Applications:
Strobes are designed to flash at 1-flash-per-second minimum over theirRegulated Input Voltage Range”
Notes: NFPA-72 specifies a flash rate of 1-to-2 flashes per second.
ADA Guidelines specify a flash rate of 1-to-3 flashes per second.
All candela ratings represent minimum-effective Strobe intensity, based on UL Standard 1971