Data Sheet for Product
7 / 12
Siem ens Variable speed drives SED2 CM1N5192en
Building Technologies 2018-02-28
Serial interface RS 485, (RS 232 optional with converter)
Protocols: USS, P1, and N2
USS transmission rate: up to 38.4 kBaud
(default 9.6 kBaud)
LON – Module optional, Profibus DP optional
As per EN 60529 IP20
Product safety
Safety of machinery; electrical equipment of
machines
EN 60204-1
Semiconductor converters. General
requirements and line commutated converters
EN 60146-1-1
Electromagnetic compatibility
EMC emissions
Electromagnetic compatibility part 3-12: Limits
for harmonic currents
EN 55011
On the power side, the integrated LHT minimizes
the network effects dramatically and thus maintains
operation within the limits of EN 61000-3-12
Adjustable speed electrical power drive systems
Part 3: EMC product standard including
specific test methods
EN 61800-3
RoHS conformity conform
Derating factors for SED2 1.5 kW… 90 kW
0 2010 30 40 50 60
[
C°
]
50
25
70
100
[
%
]
5192D02
0
Operating temperature
Permissible output current
1000 2000 3000 4000
0
80
100
%
≡
5192D03
Permissible ouput current
Installation altitude in metres above sea level
Increasing the Pulse Frequency (Switching Frequency) has the benefit of reducing the
acoustic noise of the driven motor. The downside of this is that the SED2 will generate
more heat internally within the drive. It is therefore important to observe the derating
table shown below. If full motor output shall also be ensured at higher pulse
frequencies, the VSD must be selected according to the following table.
Interface
Degree of protection of housing
Standards
Derating as a function
of the operating
temperature
Derating as a function
of the atmospheric
pressure (altitude
above sea level)
Derating as a function
of increasing the
Pulse Frequency
(P1800)