Increasing the pulse frequency will also potentially increase RFI (Radio Frequency
Interference) and therefore extra precautions in bonding and screening may be
necessary.
380 V – 480 V, ± 10%, 3 phases
IP20/IP21
filtered
IP20
unfiltered
IP54
filtered
IP54
unfiltered
Rating Pulse frequency in kHz
kW 4 6 8 10 12 14 16
Max. output current in A
SED2-1.5/32B 1.5 4 3.6 3.2 2.9 2.3 2 1.4
SED2-4/32B 4 10.2 9.2 8.2 7.1 6.1 5.1 4.1
SED2-15/32B 15 32 30.4 28.8 25.6 22.4 19.2 16
SED2-30/32B 30 62 58.9 55.8 49.6 43.4 37.2 31
SED2-45/32B 45 90 76.5 63 51.8 40.5 33.8 27
SED2-90/32B 90 178 137.9 97.9 84.5 71.1 62.3 53.3