Troubleshooting
Quick Commissioning Hand Mode Operation does not
work by default.
When commissioning is complete, if the AOP is
removed from the drive for more than five seconds, a
F0071 fault will occur.
Expected Installation Time: 5 minutes
Prerequisites
Ensure that the drive is not running during start-up and
commissioning.
Quick Commissioning
Simultaneously press and to return to the
main menu.
Use and to scroll.
Press
to confirm a selection.
Simultaneously press and to display the
parameter help screens.
Parameters
Allows you to select a parameter group (similar to
Parameter Filter P0004) and to configure individual
parameters.
1. Scroll through the list of options and highlight the
Parameters item. Confirm the selection.
2. Select Group “All Parameters”. Confirm the selection.
3. Scroll through the following parameters and enter the
required settings for AOP operation:
Parameter
Description
Parameter
Number
Index
Number
Value
User access level P0003 3
Command source P0700 1 4
USS telegram off time P2014 1 5000
Document No.125-5034
Country of Origin: US
Page 1 of 1
4. Press to return to r0000. Press to display
the standard (operate) screen.
5. Press to switch the SED2 to hand mode.
Item Number125-5034, Rev. AA
6. Press
to start the SED2.
7. Scroll to increase or decrease the output.
TIP: How to quickly change parameter values?
To quickly change a parameter value, use the following
procedure to change the single digits of the display:
1. Press and the right-hand digit blinks.
2. Scroll to change the value of this digit.
3. Press again and the next digit blinks.
4. Perform Steps 2 and 3 until the desired value
displays.
5. Press to exit the parameter value
Editing Indexed Parameters
Use the following procedure to view and edit parameters
with indexes.
1. Make certain you are in the expert access level
(P0003=3).
2. From the main menu, scroll through the list of options
and highlight the Parameters item.
Confirm the selection.
The AOP displays a parameter screen so you can
select the desired parameter group or access level.
3. Scroll through the groups/access levels and highlight
the desired parameter group. Confirm the selection?
When you select a parameter group, the AOP
displays the first parameter in ascending numerical
order.
4. Scroll through the list of parameters and highlight the
desired parameter. Confirm the parameter selection.
5. Press
again to access the parameter index. Scroll
through the indexes and highlight the desired index.
6. Press to access the index value. Scroll through
the index values and highlight the desired index
value.
7. Confirm the new index value. The AOP returns to the
parameter selection screen so you can select another
parameter, if desired.
8. To edit another indexed parameter, repeat Steps
3 to 6.
References
125-3206 SED2 AOP Operating Instructions
125-3201 SED2 VFD Installation and Start-up Guide
(SED2 Operator Panels)