Operating instructions

100/126
Siemens Building Technologies SED2 variable speed drives CM1U5192en
HVAC Products Programming 01.2002
P2221[2].
P2222[2],
P2223[2]
BI: Fixed PID setpoint select Bit 1, Bit 2, and Bit 3
Defines command source of fixed PID setpoint selection bit 1.
Unit: - Min: 0:0 Def: 0:0 (P2223[2]:722.3 Max: 4000:0
Level 3
Settings:
722.0=Digital input 1 (requires P0701 set to 99, BICO)
722.1=Digital input 2 (requires P0702 set to 99, BICO)
722.2=Digital input 3 (requires P0703 set to 99, BICO)
722.3=Digital input 4 (requires P0704 set to 99, BICO)
722.4=Digital input 5 (requires P0705 set to 99, BICO)
722.5=Digital input 6 (requires P0706 set to 99, BICO)
For P2221: For P2222: For P2223:
Index:
P2221[0]: 1st command data set (CDS)
P2221[1]: 2nd command data set (CDS)
P2222[0]: 1st command data set (CDS)
P2222[1]: 2nd command data set (CDS)
P2223[0]: 1st command data set (CDS)
P2223[1]: 2nd command data set (CDS)
r2224 CO: Act. fixed PID setpoint
Displays total output of PID fixed setpoint selection.
Unit: % Min: - Def: - Max: -
Level 3
Note:
r2224=100 % corresponds to 4000 hex.
P2225, P2227 Fixed PID setpoint mode - Bit 4 and Bit 5
Direct selection or direct selection + ON Bit 4 for PID setpoint.
Unit: - Min: 1 Def: 1 Max: 2
Level 3
Settings:
1=Direct selection 2=Direct selection + ON command 3=Binary coded selection + ON command
P2226[2]-
P2228[2]
BI: Fixed PID setpoint select Bit 4 and Bit 5
P2226[2] Min: 0:0 Def: 722:4 Max: 4000:0
P2227 Min: 1 Def: 1 Max: 2
P2228[2] Min: 0 Def: 722:5 Max: 4000:0
Level 3
Settings:
722.0=Digital input 1 (requires P0701 set to 99, BICO)
722.1=Digital input 2 (requires P0702 set to 99, BICO)
722.2=Digital input 3 (requires P0703 set to 99, BICO)
722.3=Digital input 4 (requires P0704 set to 99, BICO)
722.4=Digital input 5 (requires P0705 set to 99, BICO)
722.5=Digital input 6 (requires P0706 set to 99, BICO)
For P2226: For P2228:
Index:
P2226[0]: 1st command data set (CDS)
P2226[1]: 2nd command data set (CDS)
P2228[0]: 1st command data set (CDS)
P2228[1]: 2nd command data set (CDS)
P2231 Setpoint memory of PID-MOP
Setpoint memory.
Unit: - Min: 0 Def: 1 Max: 1
Level 3
Settings:
0=PID-MOP setpoint will not be stored 1=PID-MOP setpoint will be stored (P2240 is updated)
Dependency:
If 0 selected, setpoint returns to value set in P2240 (setpoint of PID-MOP) after an OFF command
If 1 is selected, active setpoint is 'remembered' and P2240 updated with current value.
Note:
See P2240 (setpoint of PID-MOP).
P2232 Inhibit rev. direct. of PID-MOP
Inhibits reverse setpoint selection when PID motor potentiometer is chosen either as a main
setpoint of additional setpoint (using P1000).
Unit: - Min: 0 Def: 1 Max: 1
Level 3
Details:
Inhibits reverse setpoint selection when PID motor potentiometer is chosen either as a main setpoint of additional
setpoint (using P1000)
Settings:
0=Reserve direction is allowed 1=Reserve direction inhibited
Note:
Setting 0 enables a change of motor direction using the motor potentiometer setpoint (increase/decrease frequency
either by using digital inputs or motor potentiometer up/down buttons.
P2240[2] Setpoint of PID-MOP
Setpoint of the motor potentiometer.
Allows user to set a digital PID setpoint in [%].
Unit: % Min: -200.00 Def: 10.00 Max: 200.00
Level 3
Settings:
722.0=Digital input 1 (requires P0701 set to 99, BICO)
722.1=Digital input 2 (requires P0702 set to 99, BICO)
722.2=Digital input 3 (requires P0703 set to 99, BICO)
722.3=Digital input 4 (requires P0704 set to 99, BICO)
722.4=Digital input 5 (requires P0705 set to 99, BICO)
722.5=Digital input 6 (requires P0706 set to 99, BICO)
722.6=Digital input 7 (via analog input 1, requires P0707 set to 99)
722.7=Digital input 8 (via analog input 2, requires P0708 set to 99)
19.D =Keypad UP cursor
Dependency:
To change setpoint:
1. Use UP / DOWN key on BOP or
2. Set P0702/P0703=13/14 (function of digital inputs 2 and 3)
Note:
P2240=100 % corresponds to 4000 hex.
r2250 CO: Output setpoint of PID-MOP
Displays output setpoint of motor potentiometer in [%].
Level 3