Submittal Sheet SED2 Variable Frequency Drives With E-Bypass Options
Document No. 154-051
May 9, 2011
E-Bypass –
Door Mounted
Control Devices
VFD Bypass
STOP
RESET
Input
On/Off
Enable
Input
Contactor
Output
Contactor
Bypass
Contactor
Overload
Relay
VFD
Hand
Start
Remote
Start
INTERLOCK START LOGIC
Enable Commanded Proofed
Auto Bypass Enabled
Essential Services
VFD Fault
Safety Fault
Overload Fault
Motor
VFD0097R1
Figure 1.
SED2.6 Bypass Keypad.
Typical
Specifications
SED2 E-Bypass Options
shall send the motor to
bypass mode based on an
easily accessible door-
mounted selector or based
on user's desired conditions.
LED indication of operational
state shall be provided. The
bypass mode shall provide
overload protection.
Contactors shall be
electrically and mechanically
interlocked. An essential
services mode shall send the
motor to bypass regardless
of the selected mode. When
in safety modes it should
provide indication of return
state. It should indicate
interlock sequence state
during transition. Visually
indicate faults for VFD
safety/overload.
Product Numbers
Your Product Number:
Example Product Number:
V
BE340.F130
X
Model
VB VFD with Bypass
Series
E
Electronic Bypass
Voltage
1
208 V
2 230 to 240 V
3 380 to 480 V
4 500 to 600 V
HP rating
1.0, 1.5, 2.0, 3.0, 5.0, 7.5,
10, 15, 20, 25, 30, 40, 50, 60,
75, 100, 125 [See Note 1 for these selections]
Disconnect
F
Fused Disconnect
B
Circuit Breaker
NEMA rating
1 NEMA Type 1
Contactor
3 3 Contactors
Reactor
[See Note 2]
0 None
3 Input Line Reactor
Filter
X Factory Required Designator
Options
(If no option is required, leave field blank)
Notes:
1. Available only with Voltage Codes 3 and 4.
2. Only an input line reactor can be installed in a bypass enclosure.
If a load reactor is required, a separate enclosed reactor is required.
Example Shown:
VBE340.F130X =
VBE Electronic Bypass, 480V, 40 hp, fused disconnect,
NEMA Type 1, 3 contactors, no reactor.