Data Sheet for Product
Table Of Contents
SED2 Variable Frequency Drives With E-Bypass Options Submittal Sheet
Document No. 154-051
May 9, 2011
Dimensions
Depth
With
Handle
9.6 (24)
Depth
With
Handle
12.2 (31)
Depth
With
Handle
9.6 (24)
13.2
(34)
34
(86)
48
(122)
11.5
(29)
Frame Size
A and B
Frame
Size C
12.4
(31)
10.5 TYP
(27)
10.6
(27)
11 TYP
(28)
20.8
(53)
Depth
With
Handle
10.4 (26)
53.5
(136)
Frame
Size D
19.9
(51)
11.5 TYP
(29)
1.5
(3.8)
1.5
(3.8)
2
(5)
2
(5)
4
(10)
3.4
(8.6)
57.5
(146)
45.5
(116)
Depth
17.4
(44)
Frame Size FFrame Size E
20.8
(53)
58.5
(149)
19.9
(51)
10 TYP
(25)
5.5
(14)
3
(7.6)
2.9
(7.4)
2.9
(7.4)
1
(2.5)
VFD0127R2
= Protective Shield
Siemens Industry, Inc. Page 3 of 8
Figure 2. E-Bypass Dimensions in Inches
(Centimeters).
Table 1. E-Bypass Approximate Weights.
Frame Size Weight lb (kg)
A 45 (20)
B 55 (25)
C 75 (34)
D 150 (68)
E 180 (82)
F 470 (213)
NOTE: Exact weight will be affected by actual
horsepower/voltage and selected power
options.
Table 2. E-Bypass Byass Frame Sizes and Power
Ranges.
HP kW 208/240V 480V 575V
1 .75
A
1.5 1.1
2 1.5
A
3 2.2
B
5 4
B
7.5 5.5
10 7.5
C
15 11
20 15
C
C
25 18.5
D
30 22
E
40 30
D D
50 37
60 45
F
E E
75 55
100 75
125 90
N/A F F
Table 3. E-Bypass Output Current Ratings (Amps) — Per NEC Motor Tables.
HP 1 1.5 2 3 5 7.5 10 15 20 25 30 40 50 60 75 100 125
208V
3.9 5.5 7.4 10.4 16.7 22 28 42 54 68 80 104 130 154 – – –
240V
3.9 5.5 6.8 9.6 15.2 22 28 42 54 68 80 104 130 154 – – –
480V
2.1 3.0 3.4 4.8 7.6 11 14 21 27 34 40 52 65 77 96 124 156
575V
1.4 2.1 2.7 3.9 6.1 9 11 17 22 27 32 41 52 62 77 99 125
NOTE: Drives are current rated devices. Verify that the listed ratings are ≥ the motor full load current rating.