LON Interface Option Overview
General Description
The L
ONMark® certified SED2 VFD LON
Interface Option provides direct digital control
of SED2 Variable Frequency Drives (VFDs).
The SED2 VFD can reside on a LONWorks®
network, enabling information sharing with all
other L
ONMark products from multiple vendors.
The SED2 VFD L
ON Interface Option is
LONMark-compliant with Variable Speed Motor
Drive Functional Profile Number 6010. The
SED2 VFD LON Interface Option uses standard
network variable types for communication,
allowing a SED2 VFD to be configured,
controlled, and monitored via the LONTalk®
network. A network management tool installs
the SED2 VFD on the network and binds the
network variables to other devices on the
network for seamless integration.
The L
ON Interface Option’s modular snap-on
design facilitates simple installation and
enables easy control system integration via any
existing or new SED2 VFD. The SED2 VFD
L
ON Interface Option offers a cost-effective
solution by reducing system installation and by
allowing direct integration to control systems.
Figure 1. SED2 VFD LON Interface Option.
For example, an air handling unit controller sends messages to control the start/stop and speed
reference of the SED2. The VFD outputs messages such as the actual drive speed and the
output current to the controller, operating interfaces, and energy management systems.
FAN COIL
UNIT
CONTROLLER
MOTOR DRIVE
(VARIABLE
FREQUENCY
DRIVE)
BUILDING
MANAGEMENT
SYSTEM
nvoFanSpeed
nvoDrvCurnt
nvoDrvSpeed
nviDrvSpeedStpt
nviDrvCurnt
nviDrvSpeed
Figure 2. Example of Using the SED2 VFD LON Interface Option.