Operating Instructions
Table Of Contents
- Table of Contents
- Manual Organization
- Manual Notations
- Where To Send Comments
- Reference Documents
- General Description
- LON Interface Option Functionality
- Network Variable Types and Configuration Properties
- SED2 VFD Frame Sizes A, B, and C
- SED2 VFD Frame Sizes D, E, and F
- Installation and Wiring Notes
- Setting Up SED2 VFD Parameters
- Verifying Parameter Operations
- Setting up SED2 VFD LON Interface Option
- Status LED Functionality
SED2 VFD LON Interface Option Operating Instructions
Network Variable Outputs (nvo) for Object 1
Index Network Variable
Output (nvo)
Units of
Measurement
Description
nv3 nvoDrvSpeed Percent
(0 to 100%)
Feedback drive speed.
nv5 nvoDrvCurnt Amp Feedback drive output current.
nv6 nvoDrvVolt Volt Feedback drive output voltage.
nv7 nvoDrvPwr Power-kilowatt Feedback drive output power.
nv8 nvoDrvRunHours time-hours Feedback drive total run hours.
nv9 nvoAlarm On/off switch Drive fault indication.
nv20 nvoHiPress Pressure
(-32768 Pa to 32766Pa,
Res: 1 Pa)
* Information on high pressure, which is read
from the drive register r0754[0].
nv21 nvoLoPress Pressure
(-32768 Pa to 32766 Pa,
Res: 1 Pa)
* Information on precise low pressure, which
is read from the drive register r0754[0].
nv22 nvoTemp Temperature * Information on temperature, which is read
from the drive register r0754[0].
nv23 nvoCO2 ppm * Information on CO2, which is read from the
drive register r0754[0].
nv24 nvoIAQ Percent
(0 to 100%)
* Information on IAQ, which is read from the
drive register r0754[0].
nv25 nvoEffectHiPress Pressure
(-32768 Pa to
32766 Pa, Res: 1 Pa)
* Controlled high pressure feedback, which is
read from the drive register r0754[1].
nv26 nvoEffectLoPress Pressure
(-32768 Pa to
32766 Pa,
Res: 1 Pa)
* Controlled precise low pressure feedback,
which is read from the drive register r0754[1].
nv27 nvoEffectTemp Temperature * Controlled temperature feedback, which is
read from the drive register r0754[1].
nv28 nvoEffectCO2 ppm * Controlled CO2 feedback, which is read from
the drive register r0754[1].
nv29 nvoEffectIAQ Percent
(0 to 100%)
* Controlled IAQ feedback, which is read from
the drive register r0754[1].
nv30 nvoDI1 On/off switch Status of digital input 1.
nv31 nvoDI2 On/off switch Status of digital input 2.
nv32 nvoDI3 On/off switch Status of digital input 3.
nv33 nvoDI4 On/off switch Status of digital input 4.
nv34 nvoDI5 On/off switch Status of digital input 5.
nv35 nvoDI6 On/off switch Status of digital input 6.
* Only one set of these signals may be bound at any time.
6 Siemens Building Technologies