LON Interface Option Overview
Standard Configuration Property Type (SCPTs)
The following SCPTs are network configuration property inputs (nci).
Index and
Mandatory
(M) or
Optional (O)
Configuration
Property
Language-dependent
Name
Associated
Network
Variable
(nvi, nvo)
Units of
Measurement
Description
nc37 nciLocation
Location
Entire
Object
Location label; used to provide physical
location of the node; not passed to motor
drive.
nc38 nciNmlFreq
nomFreq
Entire
Object
Nominal motor frequency.
nc39 nciRampUpTm
rampUpTm
Entire
Object
Minimum ramp up time (sec).
nc40 nciRampDownTm
rampDownTm
Entire
Object
Minimum ramp down time (sec).
nc41 nciMaxSpeed
maxSetpoint
Entire
Object
Percent
(0 to 100%)
Maximum motor speed.
nc42 nciMinSpeed
minSetpoint
Entire
Object
Percent
(0 to 100%)
Minimum motor speed.
nc43 nciMinOutTm
minSendTime
nv3
nv4
nv5
nv6
nv7
Time Minimum send time.
nc44 nciRcvHrtBt
maxRcvTime
nv1
nv2
Time Receive heartbeat time; the amount of time
that must pass before an incoming value is
considered not valid.
nc45 nciSndHrtBt
maxSendTime
nv3
nv4
nv5
nv6
Time Send heartbeat time; the minimum amount
of time that must elapse before a network
variable’s value can be propagated to the
L
ONTalk network.
nc46 nciDrvSpeedScale
defScale
nv2 Default value for nviDrvSpeedScale.
nc47 nciNmlSpeed
nomRPM
Entire
Object
Nominal motor speed in RPM; read only.