SED2 VFD LON Interface Option Operating Instructions
Parameter and Setting Value of Parameter Explanation of Value
r0754[0] for analog input 1 or
r0754[1] for analog input 2.
Read only; check scaled value.
P2280, set to 1.2. P-gain.
P2285, set to 30. I-gain.
Confirm P0700 = 6. LON communication link.
Confirm P1000 = 6.
Press P to exit programming.
14 Siemens Building Technologies