Descriptions of Parameter Settings
Descriptions of Parameter Settings
103 | 443
Time Parameters
Pr.
Explanation
Settings
Default
01-45
Time unit for acceleration /
deceleration and S-curve
0: Unit 0.01 sec.
1: Unit 0.1 sec.
0
01-46
CANopen quick stop time
Pr.01-45 = 0: 0.00–600.00 sec.
Pr.01-45 = 1: 0.0–6000.0 sec.
1.00
1.0
Sets the time required to decelerate from the maximum operation frequency (Pr.01-00) to 0.00 Hz through the
CANopen control.
Regenerative Energy Restriction Control Method
Pr.
Explanation
Settings
Default
01-49
Regenerative energy restriction
control method
0: Disable
1: Over voltage energy restriction
2: Traction energy control (TEC)
0
● 0: decelerate or stop in accordance with the original deceleration setting.
● The actual deceleration time of the motor is longer than the deceleration time setting because of the over-
voltage stall prevention.
● 1: during deceleration, the drive controls the motor according to the setting for Pr.06-01 and the recovery
voltage of the DC bus. The controller starts when the DC bus voltage reaches 95% of Pr.06-01. When Pr.06-01
is set to 0, the drive controls the motor according to the operating voltage and the recovery voltage of the DC
bus. This method decelerates according to the setting for the deceleration time. The fastest actual deceleration
time is not less than the deceleration time setting.
● 2: during deceleration, the drive controls the motor according to the setting for Pr.06-01 and the DC bus
voltage. The controller starts when the DC bus voltage reaches 95% of Pr.06-01, auto-tunes the output
frequency and the output voltage to accelerate the consumption of the regenerative energy according to the
drive’s capability, and the deceleration time is the result of the drive’s auto-tuning. Use this setting when over-
voltage occurs due to unexpected deceleration time.
Description Group 02
02 Digital Input / Output Parameters