02-00
Two-wire / three-wire operation
control
0: No function
1: Two-wire mode 1, power on for operation control
(M1: FWD / STOP, M2: REV / STOP)
2: Two-wire mode 2, power on for operation control
(M1: RUN / STOP, M2: REV / FWD)
3: Three-wire, power on for operation control
(M1: RUN, M2: REV / FWD, M3: STOP)
4: Two-wire mode 1, Quick Start
(M1: FWD / STOP, M2: REV / STOP)
5: Two-wire mode 2, Quick Start
(M1: RUN / STOP, M2: REV / FWD)
6: Three-wire, Quick Start
(M1: RUN, M2: REV / FWD, M3: STOP)
IMPORTANT
In the fast start-up function, terminal output keeps in the ready status,
and the drive responses to the command immediately.
When using Quick Start function, the output terminals UVW are with
driving voltages in order to output and respond immediately if a Start
command is given. Do not touch the terminals or modify the motor wiring
to prevent electric shocks.
1
● In the Quick Start function, the output remains ready for operation. The drive responds to the Start command
immediately.
● When using Quick Start function, the output terminals UVW are with driving voltages in order to output and
respond immediately if a Start command is given. Do NOT touch the terminals or modify the motor wiring to
prevent electric shocks.
● This parameter sets the configuration of the external drive operation control and the Quick Start function. There
are six different control modes listed in the following table.