Operating Instructions
Descriptions of Parameter Settings
Descriptions of Parameter Settings
113 | 443
Fig. 44:
● When Pr.02-09 is set to 1:
The increasing or decreasing Frequency command (F) operates according to the setting of Pr.02-10 (0.001–
1.000 Hz/ms).
● When Pr.02-09 is set to 4:
The tiered increasing or decreasing Frequency command (F) operates according to the setting of Pr.02-10
(0.001–1.000 Hz/100ms).
Pr.
Explanation
Settings
Default
02-11
Multi-function input response time
0.000–30.000 sec.
0.005