Operating Instructions
Descriptions of Parameter Settings
Descriptions of Parameter Settings
119 | 443
Settings
Functions
Descriptions
73
Over-torque 3
Activates when over-torque is detected. Pr.14-75 sets the over- torque detection level.
Pr.14-76 sets the over-torque detection time (refer to Pr.14-74–14-76).
74
Over-torque 4
Activates when over-torque is detected. Pr.14-78 sets the over- torque detection level.
Pr.14-79 sets the over-torque detection time (refer to Pr.14-77–14-79).
75
Forward RUN status
When the drive runs FWD, the output terminal for forward running is closed; when the
drive stops, the output terminal for forward running is open.
76
Reverse RUN status
When the drive runs REV, the output terminal for reverse running is closed; when the
drive stops, the output terminal for reverse running is open.
Table 10: Summary of Function Settings.
Pr.
Explanation
Settings
Default
02-18
Multi-function output direction
0000h–FFFFh (0: N.O.; 1: N.C.)
0000h
● This parameter is in hexadecimal.
● This parameter is set by a bit. If the bit is 1, the corresponding multi-function output acts in an opposite way.
Example:
Assume Pr.02-13 = 1 (indication when the drive is operating). If the output is positive, and the bit is set to 0,
then Relay is ON when the drive runs and is OFF when the drive stops. On the contrary, if the output is
negative, and the bit is set to 1, then the Relay is OFF when the drive runs and is ON when the drive stops.
bit 4
bit 3
bit 2
bit 1
bit 0
MO2
MO1
Reserved
Reserved
RY
02-19
Terminal
counting
value
reached
(returns to 0)
0–65500
0
● The counting function is enabled when Pr.02-19≠0.
● You can set the input point for the counter using the multi-function terminal MI6 as a trigger terminal (set Pr.02-
06 to 23). When counting is completed, the specified multi-function output terminal is activated (Pr.02-13,
Pr.02-16, or Pr.02-17 is set to 18).
The following timing diagram shows that when counting to 5, RY1 activates and displays 0.
Fig. 45: