Operating Instructions
Descriptions of Parameter Settings
Descriptions of Parameter Settings
121 | 443
Fig. 47:
Pr.
Explanation
Settings
Default
02-34
Output frequency setting for multi-
function output terminal
0.00–599.00 Hz
(Motor speed when using PG Card)
0.00
02-58
Multi-function output terminal
(function 42): brake frequency
check point
0.00–599.00 Hz
0.00
● Use Pr.02-34 with Pr.02-58 for the crane function and select the crane function MO #42 to set the multi-function
outputs Pr.02-13, Pr.02-16, and Pr.02-17.
● When the output frequency (H) is lower than the setting for Pr.02-58, multi-function output terminal setting 42
stops after the command breaks off.
● Pr.02-58 must be lower than Pr.02-34 when using MO=42.
● Crane application example: