Operating Instructions
Descriptions of Parameter Settings
Descriptions of Parameter Settings
122 | 443
Fig. 48:
● It is recommended that you use this with the Dwell acceleration/deceleration function as shown in the following
diagram.
Fig. 49:
Pr.
Explanation
Settings
Default
02-35
External operation control
selection after reset and reboot
0: Disable
1: Drive runs if the RUN command remains after reset or reboot
0
Setting value 1:
● Situation 1: After the drive is powered on and the external terminal for RUN stays ON, the drive runs.
● Situation 2: After clearing a fault once a fault is detected and the external terminal for RUN stays ON, you can
run the drive by pressing the RESET key.
Pr.
Explanation
Settings
Default
02-47
Motor zero-speed level
0–65535 rpm
0
● Use this parameter with MO=43 and set Pr.10-00=5.
● Use this parameter to set the motor’s speed level at zero-speed. When the actual speed is lower than this
setting, the corresponding multi-function output terminal setting 43 is ON, as shown in the diagram below.