Operating Instructions

Descriptions of Parameter Settings
Descriptions of Parameter Settings
127 | 443
Pr.
Explanation
Settings
Default
03-00
Analog input selection (AVI)
0: No function
1: Frequency command
2: Torque command (torque limit under speed mode)
3: Torque compensation command
4: PID target value
5: PID feedback signal
6: Thermistor (PTC) input value
7: Positive torque limit
8: Negative torque limit
9: Regenerative torque limit
10: Positive / negative torque limit
11: PT100 thermistor input value
12: Auxiliary frequency input
13: PID compensation value
1
03-01
Analog input selection (ACI)
0
Pr.
Explanation
Settings
Default
03-03
Analog input bias (AVI)
-100.0100.0%
0
Pr.
Explanation
Settings
Default
03-04
Analog input bias (ACI)
-100.0100.0%
0
Pr.
Explanation
Settings
Default
03-07
Positive/negative bias mode (AVI)
0: No bias
1: Lower than or equal to bias
2: Greater than or equal to bias
3: The absolute value of the bias voltage while serving as the center
4: Bias serves as the center
0
03-08
Positive/negative bias mode (ACI)