Operating Instructions
Descriptions of Parameter Settings
Descriptions of Parameter Settings
127 | 443
Pr.
Explanation
Settings
Default
03-00
Analog input selection (AVI)
0: No function
1: Frequency command
2: Torque command (torque limit under speed mode)
3: Torque compensation command
4: PID target value
5: PID feedback signal
6: Thermistor (PTC) input value
7: Positive torque limit
8: Negative torque limit
9: Regenerative torque limit
10: Positive / negative torque limit
11: PT100 thermistor input value
12: Auxiliary frequency input
13: PID compensation value
1
03-01
Analog input selection (ACI)
0
● When you use analog input as the PID reference target input, you must set Pr.00-20 to 2 (external analog
input).
– Setting method 1: Pr.03-00–03-01 set 1 as PID reference target input.
– Setting method 2: Pr.03-00–03-01 set 4 as PID reference target input.
● If the setting value 1 and setting value 4 exist at the same time, the AVI input has highest priority to become the
PID reference target input value.
● When you use analog input as the PID compensation value, you must set Pr.08-16 to 1 (source of PID
compensation value is analog input). You can see the compensation value with Pr.08-17.
● When using the Frequency command, the corresponding value for 0–10 V / 4–20 mA is 0–maximum operation
frequency (Pr.01-00).
● When using the torque command, the corresponding value for 0–10 V / 4–20 mA is 0–maximum output torque
(Pr.11-27).
● When using torque compensation, the corresponding value for 0–10 V / 4–20 mA is 0–the motor’s rated torque.
● If the settings for Pr.03-00–Pr.03-01 are the same, the AVI input has priority over the ACI input.
Pr.
Explanation
Settings
Default
03-03
Analog input bias (AVI)
-100.0–100.0%
0
Sets the corresponding AVI voltage for the external analog input 0.
Pr.
Explanation
Settings
Default
03-04
Analog input bias (ACI)
-100.0–100.0%
0
Sets the corresponding ACI current for the external analog input 0.
Pr.
Explanation
Settings
Default
03-07
Positive/negative bias mode (AVI)
0: No bias
1: Lower than or equal to bias
2: Greater than or equal to bias
3: The absolute value of the bias voltage while serving as the center
4: Bias serves as the center
0
03-08
Positive/negative bias mode (ACI)