Operating Instructions

Specifications
115V Models
13 | 443
Frame
A
C
Product Number
RT0002-11N
RT0005-11N
RT01X-11N
Applicable Motor Output [kW]
0.2
0.4
0.75
Applicable Motor Output [HP]
1/4
1/2
1
Outp
ut
Heavy
duty
Rated Output Capacity [kVA]
0.6
1.0
1.8
Rated Output Current [A]
1.6
2.5
4.8
Carrier Frequency [kHz]
2 to 15 (Default: 4)
Normal
duty
Rated Output Capacity [kVA]
0.7
1.0
2.1
Rated Output Current [A]
1.8
2.7
5.5
Carrier Frequency [kHz]
215 (Default: 4)
Input
Rated
Input
Current [A]
Heavy Duty
6.0
9.4
18
Normal Duty
6.8
10.1
20.6
Rated Voltage / Frequency
One-phase 100 to 120 Vac
(-15 to 10%), 50/60 Hz
Mains Input Voltage Range [V
AC
]
85 to 132
Mains Frequency Range [Hz]
47 to 63
Weight lbs (kg)
1.43 (0.65)
1.68 (0.74)
2.73 (1.24)
Cooling Method
Convective cooling
Fan cooling
EMC Filter
Optional
IP Rating
IP20
● The value of the carrier frequency is a factory default. Decrease the current value if
you need to increase the carrier frequency. See Derating for Ambient Temperature
and Altitude for details.
● For shock or impact load applications, select a drive with a larger capacity model.