Operating Instructions
Descriptions of Parameter Settings
Descriptions of Parameter Settings
146 | 443
Setting
Function
Description
15
Id feedback value
(2.5 × rated current) is processed as 100%.
16
Vq-axis voltage command
230V series: 250V = 100%
460V series: 500V = 100%
575V series: 625V = 100%
17
Vd-axis voltage command
230V series: 250V = 100%
460V series: 500V = 100%
575V series: 625V = 100%
18
Torque command
Motor rated torque = 100%
19
PG2 frequency command
Maximum operation frequency (Pr.01-00) is processed as 100 %.
20
CANopen analog output
For CANopen communication analog output
Terminal
Address
AFM
2026-A1
21
RS-485 analog output
For RS-485 (Modbus) control analog output
Terminal
Address
AFM
26A0H
22
Communication card analog output
For communication analog output (CMM-EIP01, CMM-PN01, CMM-DN01)
Terminal
Address
AFM
26A0H
23
Constant voltage output
Pr.03-32 controls the voltage output level.
0–100% of Pr.03-32 corresponds to 0–10V for AFM.
Table 11: Summary of Function Settings.
Pr.
Explanation
Settings
Default
03-21
Analog output gain (AFM)
0.0 to 500.0%
100.0
Adjusts the voltage level outputted to the analog meter from the analog signal (Pr.03-20) output terminal AFM of
the drive.
Pr.
Explanation
Settings
Default
03-22
Analog output in REV direction
(AFM)
0: Absolute value in output voltage
1: Reverse output 0V; forward output 0 to 10V
2: Reverse output 5 to 0V; forward output 5 to 10V
0
Fig. 60: Analog output direction selection