Operating Instructions

Specifications
460V Models
15 | 443
Weight (kg)
1.43 (0.65)
1.50 (0.68)
1.79 (0.81)
2.31 (1.05)
2.73 (1.24)
Cooling Method
Convective cooling
Fan cooling
EMC Filter
Optional
IP Rating
IP20
Frame
C
D
E
F
Product Number
RT005X-23N
RT0075-23N
RT010X-23N
RT015X-23N
RT020X-23N
Applicable Motor Output [kW]
3.7/4
5.5
7.5
11
15
Applicable Motor Output [HP]
5
7.5
10
15
20
Outp
ut
Heavy
Duty
Rated Output Capacity [kVA]
6.5
9.5
12.6
18.7
24.8
Rated Output Current [A]
17
25
33
49
65
Carrier Frequency [kHz]
2 to 15 (Default: 4)
Normal
Duty
Rated Output Capacity [kVA]
7.4
10.3
13.7
19.4
26.3
Rated Output Current [A]
19.5
27
36
51
69
Carrier Frequency [kHz]
2 to 15 (Default: 4)
Input
Rated
Input
Current [A]
Heavy Duty
20.4
30
39.6
58.8
78
Normal Duty
23.4
32.4
43.2
61.2
82.8
Rated Voltage/Frequency
Three-phase 200 to 240 Vac (-15 to 10%), 50/60 Hz
Mains Input Voltage Range [Vac]
170 to 265
Mains Frequency Range [Hz]
47 to 63
Weight lbs (kg)
2.73 (1.24)
4.56 (2.07)
1.80 (3.97)
13.78 (6.25)
Cooling Method
Fan cooling
EMC Filter
Optional
IP Rating
IP20
● The value of the carrier frequency is a factory default. Decrease the current value if
you need to increase the carrier frequency. See Derating for Ambient Temperature
and Altitude for details.
● For shock or impact load applications, select a drive with a larger capacity model.
Frame
A
B
C
Product Number
RT0005-43N
RT001X-43N
RT002X-43N
RT003X-43N
RT005X-43N
Applicable Motor Output [kW]
0.4
0.75
1.5
2.2
3.7/4
Applicable Motor Output [HP]
0.5
1
2
3
5
Outp
Heavy
Rated Output Capacity [kVA]
1.1
2.1
3.2
4.2
6.9