Operating Instructions
Descriptions of Parameter Settings
Descriptions of Parameter Settings
154 | 443
Pr.
Explanation
Settings
Default
04-65
PLC buffer 15
0–65535
0
04-66
PLC buffer 16
0–65535
0
04-67
PLC buffer 17
0–65535
0
04-68
PLC buffer 18
0–65535
0
04-69
PLC buffer 19
0–65535
0
You can combine the PLC buffer with the built-in PLC function for a variety of applications.
Description Group 05
05 Motor Parameters
indicates the parameter can be set during operation.
The following abbreviations are used in this parameter group:
● IM: Induction motor
● PM: Permanent magnet synchronous AC motor
● IPM: Interior permanent magnet synchronous AC motor
● SPM: Surface permanent magnet synchronous AC motor
Pr.
Explanation
Settings
Default
05-00
Motor parameter
auto-tuning
0: No function
1: Dynamic test for induction motor (IM)
2: Static test for induction motor (IM)
5: Rolling auto-tuning for PM (IPM / SPM)
12: FOC sensorless inertia estimation
13: High frequency stall test for PM
0
05-01
Full-load current for induction
motor 1 (A)
10–120% of the drive’s rated current
Depending on
the model
power
Sets this value according to the rated current of the motor as indicated on the motor nameplate. The default is 90%
of the drive’s rated current.
Example:
● The rated current for a 7.5 HP (5.5 kW) motor is 25 A. The default is 22.5 A.
● The setting range is 2.5–30 A (25 × 10 % = 2.5 A and 25 × 120 % = 30 A).
Pr.
Explanation
Settings
Default
05-02
Rated power for induction motor 1
(kW)
0.00–655.35 kW
Depending on
the model
power
Sets the rated power for motor 1. The default is the drive’s power value.