Operating Instructions
Descriptions of Parameter Settings
Descriptions of Parameter Settings
159 | 443
Pr.
Explanation
Settings
Default
05-31
Accumulated motor operation
time (minutes)
0–1439
0
05-32
Accumulated motor operation
time (days)
0–65535
0
Use Pr.05-31 and Pr.05-32 to record the motor operation time. To clear the operation time, set Pr.05-31 and Pr.05-
32 to 0. An operation time shorter than 60 seconds is not recorded.
Pr.
Explanation
Settings
Default
05-33
Induction motor (IM) or permanent
magnet synchronous AC motor
(PM) selection
0: IM (Induction motor)
1: SPM (Surface permanent magnet synchronous AC motor)
2: IPM (Interior permanent magnet synchronous AC motor)
0
05-34
Full-load current for a permanent
magnet synchronous AC motor
0–120% of the drive’s rated current
Depending on
the model
power
05-35
Rated power for a permanent
magnet synchronous AC motor
0.00–655.35 kW
Depending on
the motor
power
Sets the rated power for the permanent magnet synchronous AC motor. The default is the drive’s power value.
Pr.
Explanation
Settings
Default
05-36
Rated speed for a permanent
magnet synchronous AC motor
0–65535 rpm
2000
05-37
Number of poles for a permanent
magnet synchronous AC motor
0–65535
10
05-39
Stator resistance for a permanent
magnet synchronous AC motor
0.000–65.535 Ω
0.000
05-40
Permanent magnet synchronous
AC motor Ld
0.00–655.35 mH
0.00
05-41
Permanent magnet synchronous
AC motor Lq
0.00–655.35 mH
0.00
05-43
Ke parameter of a permanent
magnet synchronous AC motor
0–65535 (Unit: V / krpm)
0
05-64
Full-load current for induction
motor 3 (A)
10–120% of the drive’s rated current
Depending on
the model
power
Set this value according to the rated current of the motor as indicated on the motor nameplate. The default is 90%
of the drive’s rated current.
Example:
● The rated current for a 7.5 HP (5.5 kW) motor is 25 A. The default is 22.5 A.
● The setting range is 2.5–30 A (25 × 10 % = 2.5 A and 25 × 120 % = 30 A).
Pr.
Explanation
Settings
Default
05-65
Rated power for induction motor 3
(kW)
0.00–655.35 kW
Depending on
the model
power
Sets the rated power for motor 3. The default is the drive’s power value.