● In heavy load (Pr.00-16=1), if the DC voltage is higher than the 875 V
DC
(575V series), 700 V
DC
(460V series) or
350 V
DC
(230 series), the maximum value for Pr.06-04 is 185%.
● This is a protection for the drive to decrease output frequency automatically when the motor overloads abruptly
during constant motor operation.
● If the output current exceeds the setting value for Pr.06-04 when the drive is operating, the drive decelerates
according to the Pr.06-05 setting to prevent the motor from stalling. If the output current is lower than the
setting value for Pr.06-04, the drive accelerates (according to Pr.06-05) again to the setting frequency.
Fig. 71:
Sets the acceleration / deceleration time selection when stall prevention occurs at constant speed.
Pr.
Explanation
Settings
Default
06-05
Acceleration/deceleration time
selection for stall prevention at
constant speed
0: By current acceleration/deceleration time
1: By the first acceleration/deceleration time
2: By the second acceleration/deceleration time
3: By the third acceleration/deceleration time
4: By the fourth acceleration/deceleration time
5: By Auto-acceleration/auto-deceleration
0