Operating Instructions
Descriptions of Parameter Settings
Descriptions of Parameter Settings
167 | 443
Fig. 72:
● When you set Pr.06-06 or Pr.06-09 to 2 or 4, an ot1 / ot2 warning displays and the drive stops running after
over-torque detection. The drive does not run until you manually reset it.
Pr.
Explanation
Settings
Default
06-12
Current limit
0 to 250%
(100% corresponds to the rated current of the drive)
150
06-13
Electronic thermal relay selection
1 (motor 1)
0: Inverter motor (with external forced cooling)
1: Standard motor (motor with fan on the shaft)
2: Disabled
2
06-27
Electronic thermal relay selection
2 (motor 2)
0: Inverter motor (with external forced cooling)
1: Standard motor (motor with fan on the shaft)
2: Disabled
2
● Prevents self-cooled motor from overheating under low speed. Use an electronic thermal relay to limit the
drive’s output power.
● Setting the parameter to 0 is suitable for an inverter motor (motor fan using an independent power supply). For
this kind of motor, there is no significant correlation between cooling capacity and motor speed. Therefore, the