Operating Instructions
Descriptions of Parameter Settings
Descriptions of Parameter Settings
169 | 443
Fig. 74:
Pr.
Explanation
Settings
Default
06-15
Temperature level overheat (OH)
warning
32.0 to 212.0°F (0.0 to 110.0°C)
Depending on
the model
power
● Sets the drive’s internal IGBT overheat warning level. When the temperature is higher than Pr.06-15 setting,
the oH1 fault displays and the warning remains but it does not affect the drive operation.
● Use this parameter to check the motor overheat in advance in order to take precautionary measures to
decrease the temperature and maintain the motor’s normal operation.
● If you set the temperature 5ºC higher than the maximum setting value for Pr.06-15, IGBT overheating occurs
and the drive stops. See Chapter 14 oH1 fault descriptions for details.
Pr.
Explanation
Settings
Default
06-16
Stall prevention limit level
(Weak magnetic field current stall
prevention level)
0 to 100% (see Pr.06-03–Pr.06-04)
100
● This parameter only works in VF, VFPG, and SVC control mode.
● Sets the over-current stall prevention level when the motor’s operation frequency is larger than Pr.01-01 (base
frequency).
● Example: When Pr.06-03 = 150 %, Pr.06-04 = 100 % and Pr.06-16 = 80 %.
The over-current stall prevention level during acceleration:
Pr.06-03 * Pr.06-16 = 150 x 80 % = 120 %.
The over-current stall prevention level during operation:
Pr.06-04 * Pr.06-16 = 100 x 80 % = 80 %.
Pr.
Explanation
Settings
Default
06-17
Fault record 1
0: No fault record
1: Over-current during acceleration (ocA)
2: Over-current during deceleration (ocd)
3: Over-current during steady operation (ocn)
4: Ground fault (GFF)
6: Over-current at stop (ocS)
7: Over-voltage during acceleration (ovA)
8: Over-voltage during deceleration (ovd)
9: Over-voltage during constant speed (ovn)
10: Over-voltage at stop (ovS)
11: Low-voltage during acceleration (LvA)
12: Low-voltage during deceleration (Lvd)
13: Low-voltage during constant speed (Lvn)
14: Low-voltage at stop (LvS)
15: Phase loss protection (orP)
16: IGBT overheating (oH1)
18: IGBT temperature detection failure ( tH1o)
0
06-18
Fault record 2
0
06-19
Fault record 3
0
06-20
Fault record 4
0
06-21
Fault record 5
0
06-22
Fault record 6
0
Fault record 7 (Pr.14-70)
0