Operating Instructions

Descriptions of Parameter Settings
Descriptions of Parameter Settings
204 | 443
Pr.
Explanation
Settings
Default
08-16
PID compensation selection
0: Parameter setting
1: Analog input
0
Pr.
Explanation
Settings
Default
08-17
PID compensation
-100.0 to 100.0%
0
Pr.
Explanation
Settings
Default
08-18
Sleep mode function setting
0: See PID output command
1: See PID feedback signal
0
Pr.
Explanation
Settings
Default
08-19
Wake-up integral limit
0.0 to 200.0%
50.0
Pr.
Explanation
Settings
Default
08-21
Enable PID to change the
operation direction
0: Operation direction cannot be changed
1: Operation direction can be changed
0
08-22
Wake-up delay time
0.00 to 600.00 sec.
0.00
Pr.
Explanation
Settings
Default
08-23
PID control flag
bit 0 = 1: PID running in reverse follows the setting for Pr.00-23.
bit 0 = 0: PID running in reverse refers to PID’s calculated value.
bit 1 = 1: two decimal places for PID Kp
bit 1 = 0: one decimal place for PID Kp
2