Operating Instructions
Descriptions of Parameter Settings
Descriptions of Parameter Settings
205 | 443
wake-up delay time. When the drive reaches the wake-up delay time, it starts to catch up to reach the Frequency
command value by the acceleration time.
Fig. 95:
2) Internal PID Calculation Frequency Command (PID is in use, Pr.08-00 ≠ 0 and Pr.08-18=0.)
When the PID calculation Frequency command reaches the sleep frequency, the drive starts to count the sleep
time and the output frequency starts to decrease. If the drive exceeds the preset sleep time, then the drive is in
sleep mode (0 Hz). If the drive does not reach the preset sleep time, it remains at the lower frequency limit (if there
is a preset lower limit.), or it remains at the minimum output frequency set for Pr.01-07 and waits until it reaches the
sleep time before going into sleep mode (0 Hz). When the PID calculated Frequency command reaches the wake-
up frequency, the drive starts to count the wake-up delay time. Once it reaches the wake-up delay time, the drive
starts to catch up to reach the PID Frequency command value by the acceleration time.