Descriptions of Parameter Settings
Descriptions of Parameter Settings
209 | 443
Fig. 98:
When Pr.08-65≠0, the PID controller architecture shows as the diagram below:
Fig. 99:
When Pr.08-65 is not set to 0, Pr.00-20 is automatically set to 9.
When Pr.08-65 is set to 1, set the PID command through Pr.08-66; when Pr.08-65 is not set to 1, Pr.08-66 displays
the PID command.
When Pr.08-65 is set to 2, 4, and 6, the corresponding communication address is C2003H.
Pr.
Explanation
Settings
Default
08-66
PID target value setting
-100.00 to 100.00%
50.00
The target value setting of the PID controller (Pr.08-66) is a relative value.
Pr.
Explanation
Settings
Default
08-67
Master and auxiliary reverse
running cutoff frequency
0.0 to 100.0%
10.0
100% corresponds to Pr.01-00 the maximum operation frequency