Descriptions of Parameter Settings
Descriptions of Parameter Settings
211 | 443
Fig. 100:
Pr.
Explanation
Settings
Default
08-75
PID2 parameter switch condition
0: No switching (see Pr.08-01–Pr.08-03)
1: Auto-switch based on the output frequency
2: Auto-switch based on the deviation
0
08-76
PID2 parameter switch deviation
1
0.00 to Pr.08-77%
10.00
08-77
PID2 parameter switch deviation
2
Pr.08-76 to 100.00%
40.00
A set of PID parameters cannot meet the requirements of the entire running process in some applications. Use
Pr.08-75 to switch to the second set of PID parameters Pr.08-31–08-33. The setting method for Pr.08-31–08-33 is
the same as that for Pr.08-01–08-03.
The two sets of PID parameters switch automatically according to the frequency and deviation.
Switch according to the output frequency:
When the output frequency is between Pr.01-07 and Pr.01-00, the PID parameter is the linear interpolation value
between the two PID parameter groups.