Operating Instructions
Descriptions of Parameter Settings
Descriptions of Parameter Settings
212 | 443
Fig. 101:
Switch according to the deviation:
When the deviation absolute value between the set point and feedback is smaller than Pr.08-76 (PID2 Parameter
Switch Deviation 1), the first group PID parameters are used.
When the deviation absolute value between the set point and feedback is larger than Pr.08-77 (PID2 Parameter
Switch Deviation 2), the second group PID parameters are used.
When the deviation absolute value between the set point and feedback is between Pr.08-76 and Pr.08-77, the PID
parameter is the linear interpolation value between the two PID parameter groups.
Fig. 102:
Pr.
Explanation
Settings
Default
08-78
Allowed reverse running time after
start-up
0.0 to 6553.5 sec.
0.0
When Pr.08-78 is not set to 0, the allowed reverse running time after start-up is enabled.
When it is set to 1 second, the PID control is not allowed to change the running direction within 0–1 seconds of
starting time (Pr.08-21=0), and is allowed to change after 1 second of starting time (Pr.08-21=1).