Operating Instructions
Descriptions of Parameter Settings
Descriptions of Parameter Settings
213 | 443
Description Group 09
09 Communication Parameters
indicates the parameter can be set during operation.
When using the communication interface, the diagram on the right shows the
communication port pin definitions.
Pr.
Explanation
Settings
Default
09-00
Communication address
1 to 254
1
Sets the communication address for the drive if the AC motor drive is controlled through RS-485 serial
communication. The communication address for each AC motor drive must be unique.
Pr.
Explanation
Settings
Default
09-01
COM1 transmission speed
4.8 to 115.2 Kbps
9.6
Sets the transmission speed between the computer and the AC motor drive.
Options are 4.8 Kbps, 9.6 Kbps, 19.2 Kbps, 38.4 Kbps, 57.6 Kbps, or 115.2 Kbps; otherwise, the transmission
speed is set to the default 9.6 Kbps.
Pr.
Explanation
Settings
Default
09-02
COM1 transmission fault
treatment
0: Warn and continue operation
1: Fault and ramp to stop
2: Fault and coast to stop
3: No warning, no fault, and continue operation
3
Determines the treatment when an error is detected that the host controller does not continuously transmit data to
the AC motor drive during Modbus communication. The detection time is based on the Pr.09-03 setting.
When a transmission error occurs (for example, the error code CE10 displays), the error remains even if the
transmission status returns to normal, and is not cleared automatically. In this case, set a reset command (Reset)
to clear the error.
Pr.
Explanation
Settings
Default
09-03
COM1 time-out detection
0.0–100.0 sec.
0.0
Sets the communication time-out value.